Installation Instructions
September 2021
ACC-SVN155D-EN
Model Number: Used With:
BAYECON300* E/GBC180-300
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
Question and Answer IconNeed help?

Do you have a question about the Trane BAYECON300 Series and is the answer not in the manual?

Summary

Introduction and Safety

Warnings, Cautions, and Notices

Defines advisory types: Warning, Caution, and Notice for safety and property.

Environmental Concerns

Discusses refrigerants and their potential impact on the ozone layer.

Refrigerant Handling Practices

Outlines responsible refrigerant practices and technician certification requirements.

Field Wiring and Grounding Safety

Emphasizes qualified personnel for field wiring and adherence to electrical codes.

Personal Protective Equipment (PPE)

Details mandatory PPE for technicians to prevent injury from hazards.

EHS Policy Compliance

Stresses adherence to company Environmental, Health, and Safety (EHS) policies.

General Information

Shipping Damage Inspection

Procedures for inspecting components for shipping damage and reporting it promptly.

Parts List and Verification

Lists components for installation and advises verifying their availability.

Installation Procedures

Hazardous Service Procedures Warning

Alerts to risks associated with service and the need for strict adherence to precautions.

Field Installed Option Setup

Details the process for installing the economizer as a field-supplied option.

Trane Configuration (Field Install)

Step-by-step guide for installing the economizer for Trane configurations.

Carrier Configuration (Field Install)

Step-by-step guide for installing the economizer for Carrier configurations.

Factory Installed Option Setup

Instructions for setting up the factory-installed economizer option.

Trane Configuration (Factory Install)

Steps for configuring the factory-installed economizer for Trane systems.

Carrier Configuration (Factory Install)

Steps for configuring the factory-installed economizer for Carrier systems.

Mist Eliminator Servicing

Procedures for removing, cleaning, and reinstalling mist eliminators.

Configuration and Controls

Minimum Position Setting

How to set the minimum damper position for ventilation.

Dry Bulb Temperature Settings

Explains field selectable dry bulb changeover settings.

Reference Enthalpy Settings

Explains field selectable enthalpy changeover settings.

Electrical Wiring Connections

Guide for connecting the economizer wiring harness to the unit.

Overview

This document provides installation instructions for the 0-100% Downflow Dry Bulb Economizer, designed for use with Foundation™ Packaged Cooling and Gas/Electric units ranging from 15 to 25 Tons. The economizer is compatible with Trane model BAYECON300* and E/GBC180-300 units.

Function Description

The economizer is designed to provide free cooling by utilizing cooler outdoor air when conditions are favorable, thereby reducing the need for mechanical cooling. It features both dry bulb and enthalpy-based changeover settings to optimize energy efficiency. The unit includes an outside air damper assembly, return air damper assembly, and connecting rod assemblies for proper air mixing and control.

Important Technical Specifications

  • Compatibility: Trane BAYECON300* economizer with E/GBC180-300 Foundation™ Packaged Cooling and Gas/Electric units (15 to 25 Tons).
  • Economizer Control Options:
    • Dry Bulb (standard): Enabled by outdoor air temperature (OAT) sensor.
    • Reference Enthalpy (ReliaTel Only): Enabled by outdoor humidity (BAYENTH300*) and return humidity/temperature (BAYENTH301*) sensors.
    • Comparative Enthalpy (ReliaTel Only): Enabled when outdoor air enthalpy is 3.0 BTU/lb. less than return air enthalpy, requiring outdoor humidity, return humidity, and return temperature sensors (BAYENTH301*).
  • Dry Bulb Changeover Settings (Field Selectable):
    • A: 73°F (22.8°C)
    • B: 70°F (21.1°C)
    • C (Factory Setting): 67°F (19.4°C)
    • D: 63°F (17.2°C)
    • E: 55°F (12.8°C)
  • Enthalpy Changeover Settings (Field Selectable):
    • A: 27 Btu/lb (63 kJ/kg)
    • B: 25 Btu/lb (58 kJ/kg)
    • C (Factory Setting): 23 Btu/lb (53 kJ/kg)
    • D: 22 Btu/lb (51 kJ/kg)
    • E: 19 Btu/lb (44 KJ/Kg)
  • Field Supplied Part: Tube Sealant (Trane recommends Sikaflex 221, SEL00439) for sealing end panels.
  • Electrical Connections: Uses unit wiring harness plug PPM2A for connection to the economizer wiring harness.

Usage Features

  • Field Installed Option: The economizer kit includes an outside air damper assembly, connecting rod assemblies (Carrier and Trane configurations), return air damper assembly, block-off, and a plastic bag of miscellaneous parts (screws, outdoor air temperature sensor, edge protector, installation/operation manual, rubber grommet).
  • Factory Installed Option: For factory-installed units, a block-off and screws are provided. These units require partial assembly and setup in the field.
  • Damper Configurations: The manual details specific assembly instructions for both Trane and Carrier unit configurations, including attaching connecting rods to the return air damper and proper positioning of the damper assembly.
  • Minimum Position Setting: The economizer allows for adjustment of the minimum ventilation position using a potentiometer on the ECA (Economizer Control Assembly). This ensures a baseline amount of fresh air is always introduced when the blower circuit is energized. The damper will open to this setting each time the blower circuit is energized and will close when de-energized.
  • Sensor Installation: Includes instructions for installing the mixed air sensor, ensuring proper placement and connection to wires 121A and 122A.
  • Block-off Installation: The block-off is designed to seal the opening between the economizer and the unit base when the economizer is in its operating position, preventing unintended air leakage.

Maintenance Features

  • Mist Eliminator Servicing: The manual provides clear steps for servicing the mist eliminators, which involves removing screws from the end panel, setting the end panel aside, removing brackets, cleaning the mist eliminators, and then reinstalling them. This ensures proper air quality and system performance.
  • Inspection: Before installation, users are instructed to unpack all components, check for shipping damage, and report any concealed damage within 15 days. Photos of damage are recommended.
  • Safety Warnings: The manual emphasizes the importance of following all safety precautions, including proper field wiring and grounding, wearing personal protective equipment (PPE), and adhering to lockout/tagout procedures when servicing. It specifically warns about hazardous voltage with capacitors and the need to discharge them before servicing.
  • Environmental Concerns: Highlights the importance of responsible refrigerant practices and adherence to local and federal regulations (e.g., Federal Clean Air Act Section 608) for handling, reclaiming, recovering, and recycling refrigerants.
  • Corrosion Prevention: A notice warns against using non-recommended caulking/sealant, as it could lead to corrosion-related failures of refrigeration components. Trane recommends Sikaflex 221.