24
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
AH-SVX03C-GB
Filters
The filter cells or media (bag filters, heap filters, and roll filters) delivered separately must be installed into the unit
prior starting the unit.
Check that the filter is correctly fitted and that the entering air side of the filter is exposed to the contaminated air
stream. Refer to the certified submittals which maybe different.
If roll filters are used, check that the filter unit drive motor and the switch control are working correctly.
Humidifiers
The evaporative humidifiers with or without recirculating pump are provided with a water flow control valve.
During fan operation, with the door closed, adjust the water flow control valve to prevent water leakage from the
pump hydroscopic plastic honeycomb humidifier.
The following safety procedures are strongly recommended:
Connect the power supply to the pump.
Check that pump rotation is correct.
Check that access doors of all sections, but the one being used, are closed. The door of the section in use should be
kept in open position with a shim.
Slightly open the water flow control valve towards the humidifier.
If the humidifier is with honeycomb, ensure there is no water leakage from the honeycomb humidifier. If you
notice leakage, close the valve and check again. If it is operating correctly, open the control valve until the system
reaches its best balance.
If the humidifier is with nozzles, check that water is not coming out from the limit of humidification section and do
not spray on the casing.
Measure the absorbed power and check that it matches the data indicated on the pump name plate.
CAUTION! The above mentioned operations should be performed from outside of the unit. Do not enter the sections.
CAUTION! The pump must not be dry run to avoid any risk of overheating.
No warranty claims will be acknowledged if pump or pump motor damage is caused by a dry run.
Note: If installation and start-up do not occur immediately after delivery, take the following precautions:
Store the equipment in an area that is not exposed to excessive humidity.
Take special care to protect electrical components.
Periodically, manually turn all moving parts to avoid any blocking risks.
CAUTION! for other type of humidifier (steam, compressed water, water and compressed air, others), refer to
Manufacturer instruction and IOM.
Water quality for humidifiers and air washers
The information hereunder which refers to the water treatment is given for reference only. Water quality is of prime
concern to ensure proper operation of humidifier and air washer.
The water hardness of the freshwater has to be measured before considering any water treatment.
CAUTION! The use of improperly treated or untreated water in this equipment may result in scaling, erosion,
corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what
treatment, if any, is required.
The Trane warranty specifically excludes liability for corrosion or deterioration.
Trane assumes no responsibility for equipment damage or failure which results from the use of untreated or
improperly treated water or saline or brackish water.
Commissioning procedure