Installation
Required reprogramming of CH531 controls
Important: For a chiller retrofitted with an AFDH drive to operate correctly and efficiently, it is
critical that the actual specific nameplate data values for the chiller be entered in the
CH531 menu parameters listed in the table below (i.e. motor data and compressor
impeller data). If the unit nameplate is missing, unreadable, or of a vintage that did
not include all of the required data categories, contact Trane Technical Services
through the toll-free Trane automated phone support system at 877-788-7263 and
use the menu code sequence of 4-2-7. Provide the support person with the chiller
serial number and request a copy of the shipped-with bill of materials for this unit.
Important: Make sure your laptop is loaded with the most current version of TechView or
KestrelView software so that you have the most up-to-date version of CVR MP
firmware available to install into the DynaView.
Table 20. CH531 CVR firmware parameter settings with a retrofit AFDH
TechView Configuration View
CH531 Tab Parameter Name
Range Default Setting Recommended Setting
Starter type Not Applicable Wye-Delta Non-Comm AFD
Impeller Diameter (CPIM) 210 - 335 275 Enter CPIM from Unit Nameplate
Compressor1: Number of stages CVHE = 3, CVHF = 2 2 Enter from Unit Nameplate
Condenser Pressure Sensor Installed, Not Installed Not Installed Installed
TechView Configuration View
Starter Tab Parameter Name
Range Default Setting Recommended Setting
Restart Inhibit Stop to Start Time 0 - 255 Seconds 30 30
Surge Protection 0 = Disable, 1 = Enable 1 1
Surge Sensitivity 0 - 100% 20 20
Restart Inhibit Stop to Start Time
(or Power Loss Reset Time)
0 - 255 Seconds 30 60
Stop Delay 1 - 30 Seconds 3 30
Unit Voltage 180 - 15000 Volts 460 Enter from Unit Nameplate
Voltage Transformer Ratio 0 - 700 20 Enter from Unit Nameplate
Rated Load Amps (RLA) 0 - 2500 Amps 500 Enter from Unit Nameplate
CT Meter Scale 0 - 2000 0 Choose Correct Scale from Table 21
Current Unbalance Trip Point 15 - 100% 30 30
Current Unbalance Grace Period 10 - 255 Seconds 90 90
Maximum Acceleration Time 6 - 64 Seconds 6 6
Acceleration Shutdown Action Shutdown, Transition Shutdown Shutdown
Overload Type Exponential, Linear Linear Linear
Phase Reversal Enable, Disable Enable Disable
Contactor Integrity Test Enable, Disable Disable Disable
Phase Reversal Grace Period 20 - 1000 milliseconds 700 1000
Surge Protection Enable, Disable Enable Enable
Momentary Power Loss Enable, Disable Enable Disable