Pre-Installation
AFDH-SVN03H-EN 13
100K Short Circuit Withstand Rating
Catalog/Maximum
(a)
Amps
293 Catalog/
315 Maximum
367 Catalog/
395 Maximum
446 Catalog/
480 Maximum
545 Catalog/
588 Maximum
Incoming power to drive circuit breaker:
Number of cables per phase and
range of wire sizes lugs will accept Std Lug
Two Wire Lugs
3/0–250 KCMIL
Two Wire Lugs
400–500 KCMIL
Four Wire Lugs
4/0–500 KCMIL
Four Wire Lugs
4/0–500 KCMIL
incoming power to drive circuit breaker:
Number of cables per phase and range of wire
sizes lugs will accept Opt Lug
Two Wire Lug
2/0-250 KCMIL
One Wire Lug
2/0-500 KCMIL
N/A
Three Wire Lugs
500-750 KCMIL
Three Wire Lugs
500-750 KCMIL
Output power to compressor motor:
Number of wire cable per phase and
size of factory installed wires (unit mount)
Two
4/0 Wires
Three
4/0 Wires
Three
4/0 Wires
Three
4/0 Wires
Output power to compressor motor: Number
of cables per phase and range of wire sizes
lugs will accept (remote mount)
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
(a)Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are
allowed per discussions with product support team.
Table 3. Input/output power wire cable sizes AFDH D-Frame drives (380 V/400 V) (continued)
Table 4. Input/output power wire cable sizes AFDH D-Frame drives (575 V/600 V)
35K Short Circuit Withstand Rating
Catalog/Maximum
(a)
Amps
178 Catalog/
192 maximum
226 Catalog/
242 Maximum
271 Catalog/
290 Maximum
321 Catalog/
344 Maximum
374 Catalog/
400 Maximum
Incoming power to drive circuit breaker:
Number of cables per phase and
range of wire sizes lugs will accept Std Lug
One Wire Lug
200–500 KCMIL
Two Wire Lugs
3/0–250 KCMIL
Two Wire Lugs
3/0–350 KCMIL
Two Wire Lugs
3/0–350 KCMIL
Two Wire Lugs
3/0–350 KCMIL
incoming power to drive circuit breaker:
Number of cables per phase and range of wire
sizes lugs will accept Opt Lug
Two Wire Lug
2/0-250 KCMIL
One Wire Lug
2/0-500 KCMIL
Two Wire Lug
2/0-250 KCMIL
One Wire Lug
2/0-500 KCMIL
Two Wire Lugs
400-500 KCMIL
Two Wire Lugs
400-500 KCMIL
Two Wire Lugs
400-500 KCMIL
Output power to compressor motor:
Number of wire cable per phase and
size of factory installed wires (unit mount)
Two
3/0 Wires
Two
3/0 Wires
Two
3/0 Wires
Two
4/0 Wires
Three
4/0 Wires
Output power to compressor motor:
Number of cables per phase and range of wire
sizes lugs will accept (remote mount)
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
65K Short Circuit Withstand Rating
Catalog/Maximum
(a)
Amps
178 Catalog/
192 Maximum
226 Catalog/
242 Maximum
271 Catalog/
290 Maximum
321 Catalog/
344 Maximum
374 Catalog/
400 Maximum
Incoming power to drive circuit breaker:
Number of cables per phase and
range of wire sizes lugs will accept Std Lug
One Wire Lug
200–500 KCMIL
Two Wire Lug
3/0–250 KCMIL
Two Wire Lug
2 AWG-500
KCMIL
Two Wire Lug
2 AWG-500
KCMIL
Two Wire Lug
2 AWG-500
KCMIL
Incoming power to drive circuit breaker:
Number of cables per phase and range of wire
sizes lugs will accept Opt Lug
Two Wire Lug
2/0-250 KCMIL
One Wire Lug
2/0-500 KCMIL
Two Wire Lug
2/0-250 KCMIL
N/A N/A N/A
Output power to compressor motor:
Number of wire cable per phase and
size of factory installed wires (unit mount)
Two
3/0 Wires
Two
3/0 Wires
Two
3/0 Wires
Two
4/0 Wires
Three
4/0 Wires
Output power to compressor motor:
Number of cables per phase and range of wire
sizes lugs will accept (remote mount)
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
Two Wire Lugs
2-600 KCMIL
(a)Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-