Performance
Data
CAB-PRC001-EN 19
hot water
coils
Heating performance is based on 70°F (21°C) entering air temperature, 180°F (82°C) entering hot water temperature with a 30°F
(1°C) T. All performance measured on high speed tap, zero ESP, and a throwaway filter.
Table PD-3. Free discharge motor, group 2
heating
unit cfm TMBh gpm wpd 115V 230V 277V
size coil (l/s) (TkW) Q/ITD (l/s) (kPa) watt watt watt
2 2-row 211 (100) 14.5 (4.3) 0.13 0.97 (0.06) 4.1 (12.3) 60 95 65
3-row 201 (95) 17.7 (5.2) 0.16 1.18 (0.07) 8.8 (26.2) 60 95 65
4-row 188 (89) 18.3 (5.4) 0.17 1.22 (0.08) 2.4 (7.1) 60 95 65
3 2-row 280 (132) 19.2 (5.6) 0.17 1.28 (0.08) 7.5 (22.4) 70 80 83
3-row 277 (131) 23.3 (6.8) 0.21 1.55 (0.10) 3.2 (9.5) 85 89 101
4-row 256 (121) 24.8 (7.3) 0.23 1.65 (0.10) 4.5 (13.4) 85 89 101
4 2-row 349 (165) 23.8 (7.0) 0.22 1.58 (0.10) 2.8 (8.3) 95 96 104
3-row 338 (159) 29.4 (8.6) 0.27 1.96 (0.12) 5.5 (16.5) 100 107 106
4-row 320 (151) 31.7 (9.3) 0.29 2.11 (0.13) 7.9 (23.7) 100 107 106
6 2-row 544 (257) 37.4 (11.0) 0.34 2.49 (0.16) 7.6 (22.8) 110 154 165
3-row 541 (255) 45.4 (13.3) 0.41 3.03 (0.19) 3.6 (10.6) 125 130 124
4-row 510 (241) 49.4 (14.5) 0.45 3.29 (0.21) 4.8 (14.5) 125 130 124
8 2-row 706 (331) 47.0 (13.8) 0.43 3.13 (0.20) 3.4 (10.2) 135 150 159
3-row 659 (311) 56.8 (16.7) 0.52 3.79 (0.24) 5.9 (17.8) 120 123 133
4-row 627 (296) 61.8 (18.1) 0.56 4.12 (0.26) 8.1 (24.3) 120 123 133
10 2-row 879 (415) 60.0 (17.6) 0.55 4.00 (0.25) 5.9 (17.7) 205 250 269
3-row 886 (420) 76.4 (22.4) 0.69 5.09 (0.32) 11.4 (34.1) 225 237 230
4-row 840 (397) 82.8 (24.3) 0.75 5.52 (0.35) 15.7 (46.8) 225 237 230
12 2-row 996 (470) 69.4 (20.3) 0.63 4.62 (0.29) 8.3 (24.7) 230 246 263
3-row 976 (461) 84.3 (24.8) 0.77 5.62 (0.35) 9.0 (26.8) 220 230 239
4-row 921 (435) 91.8 (26.4) 0.83 6.12 (0.39) 10.2 (30.5) 220 230 239
Note:
1. cfm = cubic feet per minute
2. TMBh = total capacity (MBh)
3. gpm = gallons per minute
4. WPD = water pressure drop (feet of water)
5. Q/ITD = MBh (kW)/(entering water temperature - entering air temperature) when T and gpm (L/s) remain constant. To determine heating capacities at a different entering water temperature or
entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
6. Medium and low speed capacities are approximately 80% and 60% respectively of the high speed capacity.
Table PD-2. Free discharge motor, group 1
heating
unit cfm TMBh gpm wpd 115V 230V 277V
size coil (l/s) (TkW) Q/ITD (l/s) (kPa) watt watt watt
2 2-row 240 (113) 15.9 (4.7) 0.14 1.06 (0.07) 4.8 (14.4) 60 95 65
3-row 230 ( 108) 19.6 (5.7) 0.18 1.31(0.08) 10.5 (31.4) 60 95 65
4-row 210 (99) 20.1 (6.0) 0.18 1.34 (0.08) 2.8 (8.4) 60 95 65
3 2-row 318 (150) 21.0 (6.2) 0.19 1.40 (0.09) 8.8 (26.3) 70 80 83
3-row 314 (148) 25.6 (7.5) 0.23 1.70 (0.11) 3.8 (11.3) 85 89 101
4-row 284 (134) 27.1 (7.9) 0.25 1.81 (0.11) 5.3 (15.7) 85 89 101
4 2-row 388 (183) 25.6 (7.5) 0.23 1.71 (0.11) 3.2 (9.5) 95 96 104
3-row 374 (177) 31.8 (9.3) 0.29 2.12 (0.13) 6.4 (19.0) 100 107 106
4-row 350 (165) 34.2 (10.0) 0.31 2.28 (0.14) 9.1 (27.3) 100 107 106
6 2-row 611 (289) 40.6 (11.9) 0.37 2.70 (0.17) 8.9 (26.5) 110 154 165
3-row 608 (287) 49.7 (14.6) 0.45 3.31 (0.21) 4.2 (12.6) 125 130 124
4-row 565 (267) 53.8 (15.8) 0.49 3.59 (0.23) 5.7 (17.0) 125 130 124
8 2-row 790 (373) 50.9 (14.9) 0.46 3.39 (0.21) 4.0 (11.9) 135 150 159
3-row 731 (345) 61.6 (18.1) 0.56 4.11 (0.26) 6.9 (20.7) 120 123 133
4-row 688 (325) 66.8 (19.6) 0.61 4.45 (0.28) 9.4 (28.1) 120 123 133
10 2-row 980 (463) 64.8 (19.0) 0.59 4.32 (0.27) 6.8 (20.4) 205 250 269
3-row 992 (468) 83.3 (24.4) 0.76 5.55 (0.35) 13.4 (40.2) 225 237 230
4-row 930 (439) 90.1 (26.4) 0.82 6.00 (0.38) 18.3 (54.8) 225 237 230
12 2-row 1110 (524) 75.0 (22.0) 0.68 4.99 (0.32) 9.6 (28.6) 230 246 263
3-row 1082 (511) 91.5 (26.8) 0.83 6.10 (0.38) 10.5 (31.4) 220 230 239
4-row 1010 (477) 99.3 (28.5) 0.90 6.48 (0.42) 7.3 (21.8) 220 230 239