RT-SVX51H-EN
41
Table 21. Belt tension measurement and deflection ranges (in/lb)
Belts Cross
Section
Small P.D Range
(in)
Deflection Force (lb)
Super Gripbelts (in) Gripnotch (in)
Steel Cable Gripbelts
(in)
Min.
Max.
Min.
Max
Min.
Max.
A
3.0–3.6 3.00 4.50 3.87 5.50 3.25 4.00
3.8–4.8 3.50 5.00 4.50 6.25 3.75 4.75
5.0–7.0 4.00 5.50 5.00 6.87 4.25 5.25
B
3.4–4.2 4.00 5.50 5.75 8.00 4.50 5.50
4.4–5.6 5.12 7.12 6.50 9.12 5.75 7.25
5.8–8.8 6.37 8.75 7.37 10.12 7.00 8.75
Table 22. Belt tension measurement and deflection ranges (mm/kg)
Belts Cross
Section
Small P.D Range
(mm)
Deflection Force (kg)
Super Gripbelts (mm) Gripnotch (mm)
Steel Cable Gripbelts
(mm)
Min.
Max.
Min.
Max.
Min.
Max
A
13.3–16.0 13.3 20.0 17.2 24.5 14.5 17.8
16.9–21.4 15.6 22.2 20.0 27.8 16.7 21.1
22.0–31.1 17.8 24.5 22.2 30.6 18.9 23.4
B
15.1–18.7 17.8 24.5 25.6 35.6 20.0 24.5
19.6–24.9 22.8 31.7 28.9 40.6 25.6 32.3
25.8–39.1 28.4 38.9 32.8 45.0 31.1 38.9
Monthly Maintenance
Before completing the following checks, turn the unit
OFF and lock the main power disconnect switch open.
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd
rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee
ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr
lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr
ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo
ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
Filters
Inspect the return air filters. Clean or replace them if
necessary. Refer to the unit Service Facts for filter
information.
Condensate Overflow Switch
During maintenance, the switch float (black ring) must
be checked to ensure free movement up and down.
Cooling Season
Check the unit’s drain pans and condensate piping
to ensure that there are no blockages.
Inspect the evaporator and condenser coils for dirt,
bent fins, etc. If the coils appear dirty, clean them
according to the instructions described in “Coil
Cleaning” later in this section.
Manually rotate the condenser fans to ensure free
movement and check motor bearings for wear.
Verify that all of the fan mounting hardware is tight.
Inspect the F/A-R/A damper hinges and pins to
ensure that all moving parts are securely mounted.
Keep the blades clean as necessary.