50
Values for [message] are Press (+) (-) to Change Setting.
This setpoint will return to auto on any transition from
running to stop
16.1. LTSP Solution Pump AFD Speed Command. (0-100%
speed) (Related to Item 10)
Solution Pump (Status) Speed Command: xxx
(Message)
Values for Status are Auto-Default, Manual.
Values for Message are: [Press (Next)(Previous) To
Continue], or,
[xxx = xx Hz ] Where xxx is 0 to 100%
If a Limit Mode exist the Messages are: Limited Manual
Command: xxx
Status will follow the speed control setpoint and will return
to Auto on any transition from running to stop
17. Energy Input control (Auto, Manual or Slave)
Energy Input Control: (Status)
Press (+)(-) to Change Setting
Values for [Status] are Auto- Default, Manual, or Slave.
This Setpoint will return to Auto on any transition from
running to stop.
17.1 Energy Input Command: (Input Rate)
Energy Input (Status) Cmd: xxx
(Message)
(Status) Values are: Auto- Default, Manual, or, slave
[Message] values are:
If auto, Press (Next)(Previous) To Continue
If manual, Press (+)(-) to Change Setting
If slave, Press (Next)(Previous) To Continue
The (message) is as follows if in:
Auto and a Limit Exists - (Limit Mode)
Manual and a Limit Exists - Limited Manual
Command xxx, Slave and a Limit Exists - Limited
Manual Command xxx
[Status] will follow the speed control setpoint and will
return to Auto on any transition from running to stop.
18. Auxiliary heating valve Manual/auto control
(Heating units only)
Auxiliary Heat Valve Control: (Status)
Press (+)(-) to Change Setting
Values for status are: Auto-default or manual.
This setpoint will be return to auto on any transition from
running to stop.
19. If the Heat Valve control status is “Auto” the following is
displayed:
Aux Heat Valve Auto Position: xxx
(Limit Mode)
19.2. If the heat valve control status is “Manual” the
following is displayed.
When the heat valve control status is transitioned from
“Auto” to “Manual”, the manual mode target is set to the
current Heat Valve position.
Auxiliary Heat Valve Manual Position Command: xxx
Limited Manual Command: xxx
19.3. Auxiliary Heat Valve Position Indications
Aux Heat Valve Step Position: xxxxxxSteps
Aux Heat Valve Position: xxx%
xxxxx steps is the number of steps where the valve is
currently positioned.
xxx is the percent open of the set operational range.
20. Module Software Revision Identifications.
Press (Enter) to Display Software
Revision Levels or (Next) to Continue
20.1 through 20.5
If (Enter) is selected the following screen can be displayed 5
times with 5 different pairs of modules.
(Module 1) (Revision Level)
(Module 2) (Revision Level)
[Module 1,2] will be one of the following: Chiller, Circuit,
Starter, Options, Stepper 1, Stepper 2, TCI, Purge, LCLD,
and RCLD.
Revision Level will either be “number” representing the
software version number of the particular module, or, “Not
installed” if the module is not present or not
communicating on the interprocessor communications-IPC
link.