Figure 15. ABTF absorption fluid cycle sensor locations
See Table 8
Steam-Fired Absorption Unit
Steam-Fired
Generator
Condenser
HXER
High
Temperature
Generator
Pump
High
Temperature
HXER
Low
Tem-
perature
HXER
Low Temperature
Generator
Condenser
Evaporator
Absorber
Absorber
Spray Pump
Eductor
Low Temperature
Generator Pump
Evaporator Spray
Pump
Refrigerant
Storage
Purifier
Purge
1 Evaporator Entering Water Temperature - 4RT6 13 Solution Temperature Entering Level Control - 4RT2
2 Evaporator Leaving Water Temperature - 4RT7 14 Mixed Solution Temperature Entering LTHX - 4RT3
3 Condenser Leaving Water Temperature - 4RT9 15 Solution Temperature Entering Absorber - 4RT15
4 Absorber Leaving Water Temperature - 4RT8 16 Solution Temperature Leaving Absorber - 4RT14
5 Absorber Entering Water Temperature - 4RT10 17 Solution Temperature Entering LTG - 4RT16
6 Solution Temperature Leaving LTG - 4RT18 18 Solution Temperature at Absorber Sprays - 4RT13
7 Saturated Evaporator Refrigerant Temperature - 4RT12 19 Solution Temperature Entering HTG - 4RT17
8 Saturated Condenser Refrigerant Temperature - 4RT19 20 SDR Temperature Sensor - 4RT1
9 Evaporator Water Pressure Differential-optional - 4R4
10 Absorber/Cond. Water Pressure Differential-optional - 4R5
11 Interstage Vapor Pressure Transducer - 4R1
12 Solution Temperature Leaving HTG - 4RT5