EasyManua.ls Logo

Trane HORIZON ABDA - ABTF Absorption Fluid Cycle Sensor Locations; 1 Evaporator Entering Water Temperature - 4 RT6

Trane HORIZON ABDA
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
Figure 15. ABTF absorption fluid cycle sensor locations
See Table 8
Steam-Fired Absorption Unit
Steam-Fired
Generator
Condenser
HXER
High
Temperature
Generator
Pump
High
Temperature
HXER
Low
Tem-
perature
HXER
Low Temperature
Generator
Condenser
Evaporator
Absorber
Absorber
Spray Pump
Eductor
Low Temperature
Generator Pump
Evaporator Spray
Pump
Refrigerant
Storage
Purifier
Purge
1 Evaporator Entering Water Temperature - 4RT6 13 Solution Temperature Entering Level Control - 4RT2
2 Evaporator Leaving Water Temperature - 4RT7 14 Mixed Solution Temperature Entering LTHX - 4RT3
3 Condenser Leaving Water Temperature - 4RT9 15 Solution Temperature Entering Absorber - 4RT15
4 Absorber Leaving Water Temperature - 4RT8 16 Solution Temperature Leaving Absorber - 4RT14
5 Absorber Entering Water Temperature - 4RT10 17 Solution Temperature Entering LTG - 4RT16
6 Solution Temperature Leaving LTG - 4RT18 18 Solution Temperature at Absorber Sprays - 4RT13
7 Saturated Evaporator Refrigerant Temperature - 4RT12 19 Solution Temperature Entering HTG - 4RT17
8 Saturated Condenser Refrigerant Temperature - 4RT19 20 SDR Temperature Sensor - 4RT1
9 Evaporator Water Pressure Differential-optional - 4R4
10 Absorber/Cond. Water Pressure Differential-optional - 4R5
11 Interstage Vapor Pressure Transducer - 4R1
12 Solution Temperature Leaving HTG - 4RT5

Related product manuals