System Configuration and Pre-Start
OAU-SVX005C-EN 27
Table 5. Menu descriptions
Screen Menu Point List Min/Inactive Default Max/Active
BAS
Point?
Alarms
Active Alarms List of all active alarms
All Alarms List of all previous alarms
Reports
(continued
on next
page)
Custom Graphics *NOT USED*
System Status
Program Control Discharge Air Control Space ControlSpace ControlY
Heat Cool Mode Active Heat Cool N
Occupancy Status Occupied|Unoccupied|Occupied Bypass|Occupied Standby|Unknown Y
Compressor 1 Command Off On N
Compressor 2 Command Off On N
Digital Scroll Command 0% 100% N
Dehumidification Command Disabled Enabled N
Discharge Air Temperature Local Analog Input
Economizer Mode Disabled Enabled N
Evap Leaving Temp Local Analog Input
Heat Capacity 0% 100% N
Heating Output Command 0% 100% N
Heat 1 Command Off On N
Heat 2 Command Off On N
Inducer Command Off On N
Gas Valve Status Binary Input
HGRH Command 0% 100% N
OA Damper End Switch Binary Input
Outdoor Air Damper Command Closed Open N
OAD Position Local Binary Input
Outdoor Air Relative Humidity Local Analog Input
Outdoor Air Temperature Local Analog Input
Space Dewpoint Active Analog Input
Space Temperature Local Analog Input
Supply Fan Start Stop Command Off Off N
Filter Status Clean Dirty N
System Lockout Normal Normal Lockout N
UNOCC Cooling Mode Off On N
UNOCC Dehumid Mode Off On N
UNOCC Heating Mode Off On N
Discharge Airflow Local Analog Input
ERV Leaving Air Humidity Local Analog Input