EasyManua.ls Logo

Trane HUV - Page 28

Trane HUV
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28 UV-PRC001-EN
Filter Maintenance
Filter status for the controller is
based on the cumulative run hours
of the unit fan. The controller com-
pares the amount of fan run time
against an adjustable fan run hour
(stored in the controller) to deter-
mine when maintenance is recom-
mended for the unit. The run-
hours value may be user edited as
required (through Rover). The val-
id range for the fan run hours limit
is 0 to 5000 hours with a default of
600 hours. Once the run hours lim-
it has been exceeded, the control-
ler generates a maintenance
required diagnostic (unit will not
shut-down). The user will be noti-
fied of this diagnostic through the
building automation system or
when a Trane Service Tool is com-
municating with the controller.
Master Slave
(Data Sharing)
Because the ZN520 controller uti-
lizes LonWorks
TM
technology, the
controller can send or receive data
(setpoint, heat/cool mode, fan re-
quest, space temperature, etc.) to
and from other controllers on the
communication link with or with-
out the existence of a building au-
tomation system. This applies to
applications where multiple units
might share one zone sensor for
both stand-alone (with communi-
cation wiring between units) and a
building automation system. See
Figure 27 for ZN520 master
slave system layout.
Controls
Tracer ZN520
Manual Output Test
The ZN520 controller includes a
manual output test function. This
function may be initiated from the
blue test push button on the con-
troller or through Rover
TM
. This
feature is used to manually exer-
cise the outputs in a defined se-
quence.
The purpose of this test sequence
is to verify output and end device
operation. The manual output test
function may also be used in the
following situations:
• Reset latching diagnostics
• Verify output wiring and op-
eration
• Force the water valve(s) open
to balance the hydronic sys-
tem during installation set-
up or service.
Figure 27: ZN520 master slave system

Other manuals for Trane HUV

Related product manuals