10
*
*
*
*
*
HEATER MODEL NUMBER DIGITS ‘*’: A , B
5. AIRFLOW PERFORMANCE (OXBOX AIR HANDLERS ARE SUITABLE FOR MOBILE
HOME APPLICATIONS)
Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size.
External static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat
operation.
AIRFLOW PERFORMANCE DATA
Electric Heater Kits
NO.
Kit# Description Ref. Air Handler use
1
5kW Heat Strip
18,24,30,36,42,48,60
2
7.5kW Heat Strip
3
10kW Heat Strip
4
5
15kW Heat Strip, Double Breaker panel
20kW Heat Strip, Double Breaker panel
36,42,48,60
30,36,42,48,60
0[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]
CFM 563 498 434 373 317 246 217 / /
Watts 148 144 143 138 135 130 126 / /
Current/A 0.64 0.61 0.58 0.57 0.54 0.51 0.47 / /
CFM 695 633 576 509 457 388 318 240 231
Watts 167 166 163 161 157 153 150 143 138
Current/A 0.8 0.79 0.78 0.77 0.76 0.68 0.64 0.62 0.61
CFM 927 872 815 761 697 633 566 510 380
Power/W 307 302 297 292 286 280 274 269 257
Current/A
1.45 1.43 1.41 1.4 1.38 1.35 1.33 1.32 1.29
CFM
Watts
Current/A
CFM
Watts
Current/A
CFM
Power/W
Current/A
CFM
999 953 905 847 757 681 610 543 411
Watts
316 310 306 302 288 279 270 256 240
Current/A
1.3
8 1.36 1.34 1.32 1.28 1.24 1.21 1.16 1.10
CFM
1176 1127 1086 1028 944 842 746 668 569
Watts
342 336 334 326 315 303 292 281 266
Current/A
1.49 1.47 1.45 1.42 1.38 1.33 1.29 1.25 1.19
CFM
1409 1359 1306 1253 1192 1108 986 870 743
Power/W
456 446 438 429 419 404 384 368 348
Current/A
2.01 1.96 1.93 1.90 1.86 1.80 1.73 1.67 1.61
CFM
1028 985 930
859 781 712 649 571 468
Watts
362 353 345 335 323 313 303 290 276
Current/A
1.64 1.62 1.60 1.57 1.54 1.51 1.49 1.45 1.42
CFM
1315 1266 1208 1146 1065 981 866 775 686
Watts
406 399 392 385 372 361 344 331 320
Current/A
1.82 1.80
1.78 1.75 1.72 1.69 1.65 1.62 1.59
CFM
153
2 1478 1421 1347 1284 1184 1082 932 805
Power/W
524 513 502 491 478 462 446 423 407
Current/A
2.39 2.36 2.34 2.31 2.28 2.23 2.2 2.14 2.11
30
Low
Medium
High
Model
Number
Motor
Speed
18
Low
Medium
High
External Static Pressure-Inches W.C.[kPa]
CFM Wet Coil without filter and Electric Heat
36
Low
Medium
High
24
Low
Medium
High
666 634 597 558 506 459 407 326 267
210 205 201 196 191 185 178 167 159
0.92 0.89 0.88 0.86 0.84 0.82 0.79 0.75 0.72
855 835 791 744 705 657 586 528 464
240 237 232 227 222 215 207 200 191
1.04 1.02 1.01 0.98 0.96 0.94 0.91 0.87 0.84
980 950 905 869 810 757 687 609 523
308 302 298 293 282 273 262 252 240
1.34 1.31 1.29 1.27 1.23 1.19 1.16 1.117 1.07