EasyManuals Logo

Trane Precedent User Manual

Trane Precedent
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
23RT-PRC006-EN
(3 - 4 Tons)
High Efficiency
Table GD-5 — General Data
3 Ton Convertible Units 4 Ton Convertible Units
YHC036A1, A3, A4, AW YHC048A1, A3, A4, AW
Cooling Performance
1
Gross Cooling Capacity 38,000 49,800
SEER
2
12.50 12.0
Nominal CFM / ARI Rated CFM 1,200 / 1,200 1,600/1,600
ARI Net Cooling Capacity 36,600 47,500
System Power (KW) 3.33 4.48
Heating Performance
3
Heating Models Low Medium High Low Medium High
Heating Input (Btu) 60,000 80,000 120,000 60,000 80,000 120,000
Heating Output (Btu)
7
48,000 64,000 96,000 48,000 64,000 96,000
AFUE %
4 8
81 81 81 81 81 81
Steady State Efficiency (%)
8
81 81 81 81 81 81
No. Burners 2 2 3 2 2 3
No. Stages 1 1 1 1 1 1
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 1/2 1/2 1/2
Compressor
No./Type 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
5
83 85
Outdoor Coil - Type Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125
Face Area (sq ft) 7.19 9.59
Rows/FPI 2/17 3/17
Indoor Coil - Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq ft) 6.68 6.68
Rows/FPI 3/16 4/16
Refrigerant Control Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT
Outdoor Fan - Type Propeller Propeller
No. Used/Diameter (in.) 1/22 1/22
Drive Type/No. Speeds Direct/1
14
Direct/1
14
CFM 2,550 3,050
No. Motors/HP 1/0.20 1/0.33
Motor RPM 1,075 1,075
General
Data

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Precedent and is the answer not in the manual?

Trane Precedent Specifications

General IconGeneral
RefrigerantR-410A
TypePackaged
StagesSingle
Voltage208/230V or 460V
Heating OptionsElectric or Gas