EasyManuals Logo

Trane Precedent User Manual

Trane Precedent
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
75RT-PRC006-EN
Performance
Data
Table PD-91 — Gas-Fired Heating Capacities
Unit Heating Heating Air Temp.
Tons Efficiency Model No. Input MBH
1
Output MBH
1
Rise, F
Y*C036A1*L 60.0 47.0 25-55
Y*C036A3, A4, AW*L 60.0 48.0 25-56
Standard and Y*C036A1*M 80.0 63.0 35-65
3
High Efficiency Y*C036A3, A4, AW*M 80.0 64.0 35-65
Y*C036A1*H 120.0 95.0 55-85
Y*C036A3, A4, AW*H 120.0 96.0 55-85
Y*C048A1*L, 60.0 47.0 15-45
Y*C048A3, A4, AW *L 60.0 48.0 15-45
Standard and Y*C048A1*M 80.0 63.0 20-50
4
High Efficiency Y*C048A3, A4, AW*M 80.0 64.0 20-50
Y*C048A1*H 120.0 95.0 40-70
Y*C048A3, A4, AW *H 120.0 96.0 40-70
YSC060A1*L 60.0 47.0 10-40
YSC060A3, A4, AW, AK*L 60.0 48.0 10-40
YSC060A1*M 80.0 63.0 15-45
Standard Eff. YSC060A3 A4, AW*M 80.0 64.0 15-45
YSC060A1*H 130.0 103.0 35-65
YSC060A3, A4, AW, AK*H 130.0 104.0 35-65
5
YHC060A1*L 60.0 47.0 10-40
YHC060A3, A4, AW, AK*L 60.0 48.0 10-40
High Eff.
YHC060A1*M 80.0 63.0 15-45
YHC060A3,A4,AW*M 80.0 64.0 15-45
YHC060A1*H 130.0 103.0 35-65
YHC060A3, A4, AW, AK*H 130.0 104.0 35-65
Standard and
Y*C072A1, A3, A4, AW, AK*L 80.0 64.8 15-45
6
High Efficiency
Y*C072A1, A3, A4, AW*M 120.0/84 97.2/68 20-50
Y*C072A1, A3, A4, AW, AK*H 150.0/105 121.5/85 25-55
Standard and
Y*C090,092A1, A3, A4, AW, AK*L 120.0/84 97.2/68 20-50
High Efficiency
Y*C090,092A1, A3, A4, AW*M 150.0/105 121.5/85 25-55
Y*C090,092A1, A3, A4, AW, AK*H 200.0/140 162.0/113 35-65
Standard and
Y*C102A1, A3, A4, AW, AK*L 120.0/84 97.2/68 15-45
High Efficiency
Y*C102A1, A3, A4, AW*M 150.0/105 121.5/85 20-50
Y*C102A1, A3, A4, AW, AK*H 200.0/140 162.0/113 35-65
Standard and
Y*C120A1, A3, A4, AW, AK*L 150.0/105 121.5/85 20-50
10
High Efficiency
Y*C120A1, A3, A4, AW*M 200.0/140 162.0/113 25-55
Y*C120A1, A3, A4, AW, AK*H 250.0/175 202.5/141.8 35-65
Ratings shown are for elevations up to 2,000 ft. For higher elevations, reduce ratings at a rate of 4% per 1,000 ft. elevation.
Note:
1. For two stage heaters, Second stage is total heating capacity. Second Stage / First Stage.
Table PD-90— Outdoor Sound Power Level - dB (ref. 10
-12
Watts)
Unit Octave Center Frequency Overall
Tons Model No. 63. 125 250 500 1000 2000 4000 8000 dBA
3 Y*C036A 86 83 81 80 78 74 69 68 83
YSC048A1 92 87 84 83 81 76 72 69 86
4 YSC048A3,A4,AW 90 84 78 77 76 72 70 68 82
YHC048A 92 86 83 82 81 75 72 69 85
YSC060A 94 87 83 82 79 75 73 69 84
5 YHC060A 94 87 82 81 78 74 72 69 84
YSC072A 90 94 90 87 83 78 74 67 88
6 YHC072A 91 95 90 87 84 79 75 68 89
YSC090A 92 95 91 88 84 80 75 68 90
7½ YSC092A 89 93 88 85 81 76 72 66 87
YHC092A 92 96 92 89 85 80 76 69 91
YSC102A 88 92 87 84 80 75 72 65 86
8½ YHC102A 91 95 90 87 84 79 75 68 89
YSC120A 91 88 84 82 81 76 73 67 86
10
YHC120A 94 89 87 85 84 78 75 69 88
Note:
Tests follow ARI270-95.
*Indicates both standard and high efficiency airflow.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Precedent and is the answer not in the manual?

Trane Precedent Specifications

General IconGeneral
RefrigerantR-410A
TypePackaged
StagesSingle
Voltage208/230V or 460V
Heating OptionsElectric or Gas

Related product manuals