Performance
Data
(6 Ton)
Standard Efficiency
Table PD-35 — Belt Drive Evaporator Fan Performance — 6 Ton — YSC072AK *H— High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std. Motor & Field Supplied Low Static Drive 2 HP Standard Motor & Drive
1920 559 0.32 618 0.39 668 0.46 715 0.53 759 0.61 802 0.69 842 0.77 881 0.85 917 0.93
2160 600 0.42 654 0.49 705 0.57 749 0.65 791 0.73 831 0.81 870 0.90 907 0.99 943 1.08
2400 594 0.46 644 0.53 692 0.61 741 0.70 786 0.79 826 0.88 864 0.97 900 1.05 936 1.15 971 1.24
2640 643 0.60 691 0.67 734 0.76 778 0.85 822 0.95 862 1.05 899 1.14 935 1.24 967 1.33 1001 1.43
2880 693 0.76 737 0.84 778 0.93 818 1.03 858 1.13 898 1.24 935 1.35 970 1.45 1003 1.55 1034 1.66
2 HP Standard Motor
& High Static Drive
Table PD-35 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive
1920 952 1.01 985 1.09 1019 1.17 1050 1.26 1080 1.34 1110 1.42 1139 1.51 1167 1.60 1192 1.68 1220 1.77
2160 977 1.17 1010 1.26 1043 1.36 1073 1.44 1103 1.53 1133 1.63 1161 1.72 1189 1.81 1216 1.91 1242 2.00
2400 1004 1.34 1037 1.44 1068 1.55 1099 1.65 1128 1.75 1156 1.85 1185 1.95 1212 2.05 1239 2.16 1265 2.26
2640 1033 1.54 1064 1.64 1095 1.75 1125 1.87 1153 1.97 1182 2.09 1210 2.20
2880 1065 1.76 1096 1.88 1124 1.99 1153 2.10 1182 2.22 ———————
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-34 — Belt Drive Evaporator Fan Performance — 6 Ton — YSC072AK *L — Low Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
1920 583 0.35 638 0.42 687 0.49 732 0.56 777 0.64 817 0.71 857 0.80 895 0.88
2160 559 0.36 613 0.43 666 0.51 715 0.59 759 0.67 800 0.75 841 0.83 879 0.92 915 1.01
2400 597 0.46 647 0.54 695 0.62 743 0.71 788 0.80 828 0.88 866 0.97 902 1.06 938 1.15
2640 585 0.49 636 0.59 684 0.66 728 0.75 772 0.84 815 0.94 856 1.03 894 1.13 930 1.23 963 1.32
2880 629 0.63 677 0.73 722 0.81 763 0.89 803 0.99 844 1.09 884 1.20 923 1.31 958 1.41 990 1.51
Table PD-34 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Drive 2 HP Standard Motor & High Static Drive)
1920 931 0.96 965 1.04 999 1.12 1030 1.20 1062 1.29 1092 1.37 1120 1.45 1150 1.54 1177 1.63 1204 1.71
2160 951 1.10 984 1.19 1018 1.29 1049 1.37 1080 1.46 1110 1.55 1139 1.65 1168 1.74 1196 1.84 1222 1.93
2400 973 1.25 1006 1.35 1039 1.45 1070 1.55 1100 1.65 1129 1.76 1158 1.86 1186 1.96 1213 2.06 1241 2.16
2640 996 1.42 1029 1.52 1060 1.63 1091 1.74 1121 1.85 1150 1.96 1178 2.07 1206 2.18 1233 2.30
2880 1023 1.62 1054 1.72 1085 1.83 1114 1.95 1143 2.06 1172 2.18 1200 2.30