EasyManua.ls Logo

Trane Precedent - Page 66

Trane Precedent
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RT-PRC006-EN66
Performance
Data
(7½ Ton)
High Efficiency
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-72 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 858 1.43 888 1.57 917 1.71 945 1.85 971 1.99 998 2.14 1023 2.28 1048 2.44 1072 2.59 1095 2.75
2700 886 1.60 915 1.75 942 1.90 969 2.05 995 2.21 1020 2.36 1045 2.51 1069 2.67 1093 2.83 1117 3.00
3000 916 1.79 944 1.94 970 2.10 995 2.26 1020 2.43 1044 2.59 1069 2.76 1092 2.93 1116 3.10 1139 3.27
3300 947 2.01 974 2.16 1000 2.33 1026 2.50 1050 2.67 1073 2.84 1097 3.02 1119 3.20 1141 3.38
3600 976 2.25 1004 2.42 1030 2.58 1056 2.76 1080 2.94 1103 3.12 1126 3.30
3-HP Oversized Motor & Drive
Table PD-72 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *L,M — Low and Medium Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 613 0.58 656 0.68 696 0.79 732 0.91 765 1.03 798 1.16 829 1.30
2700 605 0.58 647 0.69 687 0.81 726 0.93 762 1.05 796 1.18 828 1.32 857 1.45
3000 606 0.62 645 0.72 684 0.83 721 0.96 758 1.09 792 1.22 826 1.36 858 1.49 888 1.64
3300 609 0.66 650 0.77 688 0.89 723 1.00 758 1.13 792 1.27 825 1.41 857 1.56 888 1.70 918 1.85
3600 658 0.84 695 0.96 731 1.08 764 1.20 796 1.33 828 1.47 859 1.63 890 1.79 920 1.94 949 2.10
2-HP Standard Motor & Drive
Table PD-73 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *H — High Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 623 0.60 664 0.70 703 0.82 739 0.93 773 1.06 804 1.19 835 1.32
2700 617 0.61 658 0.73 698 0.84 736 0.96 771 1.08 804 1.21 835 1.35 865 1.49
3000 619 0.65 658 0.75 696 0.87 733 1.00 770 1.13 804 1.26 837 1.40 868 1.54 897 1.69
3300 625 0.70 666 0.82 702 0.93 737 1.05 771 1.19 805 1.33 838 1.47 870 1.62 900 1.76 929 1.91
3600 675 0.89 713 1.02 747 1.14 779 1.26 811 1.40 843 1.55 874 1.70 904 1.86 934 2.02 962 2.17
2-HP Standard Motor & Drive
Table PD-73 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 864 1.46 895 1.60 923 1.74 951 1.88 977 2.02 1003 2.17 1028 2.32 1053 2.47 1078 2.63 1100 2.78
2700 894 1.64 921 1.79 948 1.94 974 2.09 1001 2.24 1027 2.40 1052 2.56 1076 2.72 1100 2.88 1124 3.05
3000 925 1.83 952 1.99 978 2.15 1004 2.32 1029 2.48 1052 2.65 1076 2.82 1100 2.99 1123 3.15 1146 3.33
3300 958 2.06 984 2.22 1010 2.39 1035 2.56 1059 2.73 1082 2.91 1105 3.09 1128 3.28
3600 990 2.33 1017 2.50 1043 2.66 1067 2.84 1091 3.02 1114 3.20 1137 3.39
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table of Contents