EasyManua.ls Logo

Trane RTAA-155 - Menu 5 - Factory Display #2; Number of Compressors; Compressor Tons; Fans Per Circuit

Trane RTAA-155
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
104
RTAA-IOM-3
Menu 5 – Factory Display #2
50 - Number of Compressors: Set to
the number of compressor installed in
the unit.
51 - Compressor Tons: Set to the rating
in tons, of the each installed
compressor. See Table 2.
52 - Low Water Temperature EXV Gain
Compensation: Set to “E” if the unit
will ever operate with a leaving chilled
water temperature of 40 F or less.
53 - Fan Control: Set to “E”.
54 - Fans Per Circuit: Establishes the
number of fans installed on each
circuit. See Figures 45 and 46.
55 - Reduced Inrush Starting: Set to
“d” if across-the-line wiring or to “E” if
Wye-Delta wiring.
56 - Compressor Current Overload
Setting: Establishes the compressor
motor current overload setting, which
must agree with the DIP Switch
settings on the corresponding
compressor modules. See Table 16.
Compressor Compressor Module
A ................................. 1U4
B.................................. 1U5
C.................................. 1U6
D ................................. 1U7
57 - GP Compressor Unit: This menu
item must be set to “d”. The unit is not
to be operated unless a “d” is
displayed in this item.
58 - Low Ambient, Half Airflow Fan
(Halfpitch Blades on Lead Fan(s): Set
this menu item per the following unit
selections
RTAA 130 - 200 Standard Ambient = d
RTAA 130 - 200 Low Ambient = E
RTAA 240 - 400 All = E
59 - LATSM: Set this menu item to “d”.
5A - NNS: Set this menu item to “d”.
5b - Number of EXV Valves per Circuit:
Set this menu item per the following
unit selections
RTAA 130 - 200 Circuit 1 = 1
Circuit 2 = 1
RTAA 240 - 300 Circuit 1 = 2
Circuit 2 = 1
RTAA 340 - 400 Circuit 1 = 2
Circuit 2 = 2
5C - Future Option: Set this menu item
to “d” for both Circuit #1 and Circuit #2.
Table 16
Compressor Overload DIP Switch Settings
Overload Setting
Compressor CT DIP Sw/Decimal**
Tons Volts.Hz RLA Ext* 12345
70 200/230.60 280 -05 00100/04
460.60 122 -02 10000/16
575.60 98 -01 11110/30
85 200/230.60 306 -05 01011/11
460.60 133 -02 10110122
575.60 107 -02 00110/06
100 200/230.60 375 -05 11010/26
460.60 163 -03 10000/16
575.60 131 -02 10110122
*The CT base part number is X13580253. The numbers in this column are suffixes to the
base number.
**On the DIP switch, 1= ON, O= OFF. The decimal number is the setting Menu Item 56. The
DIP switch setting and the decimal display of Item 56 comprise a redundant overload
setting. If the values are not set to match, the related compressor(s) will continue to run,
but a diagnostic will be initiated, both settings will be ignored, and the UCM will use the
lowest possible trip setting value.

Table of Contents

Related product manuals