Installation - Electrical
RTAD-SVX01F-E4 47
Table 31 - General electrical data
Unit Size
RTAD 085 FC STD 400/3/50 150 1600 35
RTAD 100 FC STD 400/3/50 150 1600 35
RTAD 115 FC STD 400/3/50 150 1600 35
RTAD 125 FC STD 400/3/50 150 1600 35
RTAD 145 FC STD 400/3/50 150 1600 35
RTAD 150 FC STD 400/3/50 150 1600 35
RTAD 165 FC STD 400/3/50 150 1600 35
RTAD 180 FC STD 400/3/50 150 1600 35
RTAD 085 FC HE 400/3/50 150 1600 35
RTAD 100 FC HE 400/3/50 150 1600 35
RTAD 115 FC HE 400/3/50 150 1600 35
RTAD 125 FC HE 400/3/50 150 1600 35
RTAD 145 FC HE 400/3/50 150 1600 35
RTAD 150 FC HE 400/3/50 150 1600 35
Table 32 - Electrical connections
Unit Size
RTAD 085 FC STD 6 x 125 250 95 150
RTAD 100 FC STD 6 x 160 400 185 240
RTAD 115 FC STD 6 x 200 400 185 240
RTAD 125 FC STD 6 x 250 500 240 240
RTAD 145 FC STD 6 x 250 500 240 240
RTAD 150 FC STD 6 x 250 630 2 x 150 2 x 300
RTAD 165 FC STD 315 + 250 630 2 x 150 2 x 300
RTAD 180 FC STD 6 x 315 630 2 x 150 2 x 300
RTAD 085 FC HE 6 x 125 250 95 150
RTAD 100 FC HE 6 x 160 400 185 240
RTAD 115 FC HE 6 x 200 400 185 240
RTAD 125 FC HE 6 x 250 500 240 240
RTAD 145 FC HE 6 x 250 500 240 240
RTAD 150 FC HE 6 x 250 630 2 x 150 2 x 300
(1) To take in account for the sizing of power cables
Table 33 - Hydraulic module electrical data
Single or dual pump
Pump 1 Pump 2 Pump 3 Pump 4
Standard Efficiency unit
145 kW (1) 5.0 6.5 9.2 12.1
150 kW (1) 5.1 6.8 9.7 12.7
165 kW (1) 5.1 7.1 10.1 13.2
180 kW (1) 5.2 7.3 10.5 13.6
High Efficiency unit
115 kW (1) 4.7 5.9 8.3 11.0
125 kW (1) 4.9 6.4 9.1 12.0
145 kW (1) 5.0 6.6 9.3 12.2
150 kW (1) 5.1 6.8 9.7 12.6
All sizes
Maximum amps (A) 10.3 13.8 20 26.5
Power factor 0.89 0.89 0.88 0.88
(1) Power input at Eurovent conditions: Ambient temperature 35°C, water temperature 12/7°C
Crankcase heater
Compressor
(W)
Short circuit intensity
(kA)
Compressor
fuse size (1)
(A)
Disconnect
switch size (1)
(A)
Minimum connecting
wire (1)
(mm²)
Maximum connecting
wire (1)
(mm²)
Nominal voltage
(V/Ph/Hz)
Control circuit
(VA)