Carbon rupture disk and gaskets removed and
discarded.
Proper adapters utilized with proper sealant
(Loctite® 242 or Loctite® 277) or welded.
Excess flow valve installed horizontally; refer to
figures in “Overview,” p. 7.
Pressure gauge installed; refer to figures in
“Overview,” p. 7.
Pressure switch installed (when selected); refer to
figures in “Overview,” p. 7.
Purge discharge line connected to the downstream
side piping to vent purge exhaust out the vent line
to the outdoors and no u-traps created in this line.
Drip leg and drain present.
Pressure test RuptureGuard installation using 5
psig (34.5 kPaG) dry nitrogen.
Chiller nitrogen holding charge applied (5 psig [34.5
kPaG]).