20 RT-SVP07B-EN
General Status Display
Min Voltage
2 VDC ___________ Setup
Supply Fan IGV/VFD (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
30/0 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC ___________ Setup
Return Fan VFD (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60/0 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC ___________ Setup
Exhaust Damper/VFD (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
0 VDC ___________ Setup
Hydronic Heat (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC ___________ Setup
Low Ambient Damper Ckt-1 (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC ___________ Setup
Low Ambient Damper Ckt-2 (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC ___________ Setup
Cond Fan VFD Ckt -1(if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
0 VDC ___________ Setup
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
Adjustable Function Factory Preset Changed To
To adjust
press...