RT-SVP07B-EN 23
General Status Display
Supply Air Low Limit 50 F ___________ Setpoints
VCM Preheat Actuate Temp 35 F ___________ Setpoints
Design Min CO
2
(DCV) 1000 PPM ___________ Setpoints
DCV Min CO
2
800
1
/400
2
PPM ___________ Setpoints
Design Min OA Flow (DCV) 220 CCFM ___________ Setpoints
DCV Min OA Flow 67 CCFM ___________ Setpoints
DCV Min OA Flow Deadband 5 CCFM ___________ Setpoints
Min OA Flow w\ VCM Set per unit size ___________ Setpoints
Min OA Flow Deadband Set per unit size ___________ Setpoints
Design Min OA Damper Position (DCV) 15 % ___________ Setpoints
DCV Min OA Damper Position 5 % ___________ Setpoints
OA Damper Min Position (non-DCV) 15 % ___________ Setpoints
OAD Min Position w/IGV/VFD at 0% 25% ___________ Setpoints
OAD Min Position w/IGV/VFD at 50% 20% ___________ Setpoints
OAD Min Position w/IGV/VFD at 100% 15% ___________ Setpoints
OAD Min Position (Default) 15% ___________ Setpoints
Supply Air Pressure 2.0 IWC ___________ Setpoints
Supply Air Pressure High Limit 4.0 IWC ___________ Setpoints
Supply Air Pressure Deadband 0.5 IWC ___________ Setpoints
Max Return Plenum Pressure 0.8 IWC ___________ Setpoints
Return Plenum Pressure Deadband 0.1 IWC ___________ Setpoints
Space Pressure - Setpoint 0.08 IWC ___________ Setpoints
Space Pressure - Deadband .04 IWC ___________ Setpoints
Space Pressure Low Limit -0.2 IWC ___________ Setpoints
Exhaust Enable Point 25 % ___________ Setpoints
Exhaust Inhibit Point DISABLE ___________ Setpoints
Low Ambient Comp. Lockout (Standard Units) 50 F ___________ Setpoints
Low Ambient Comp. Lockout (Low Ambient Units) 0 F ___________ Setpoints
Standby Freeze Avoidance 0 % ___________ Setpoints
Recovery Frost Avoidance Setpoint 27 F ___________ Setpoints
Setpoint Source Selection For...
Supply Air Temp Cooling Hi Default ___________ Setpoints
Supply Air Temp Heating Hi Default ___________ Setpoints
Occupied Zone Cooling Hi Default ___________ Setpoints
Occupied Zone Heating Hi Default ___________ Setpoints
Unoccupied Zone Cooling Hi Default ___________ Setpoints
Unoccupied Zone Heating Hi Default ___________ Setpoints
Morning Warm-Up Hi Default ___________ Setpoints
Economizer Dry Bulb Enable Hi Default ___________ Setpoints
Outside Damper Minimum Position Hi Default ___________ Setpoints
Occupied Dehumidification Hi Default ___________ Setpoints
Unoccupied Dehumidification Hi Default ___________ Setpoints
Supply Air Reheat Hi Default ___________ Setpoints
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
Adjustable Function Factory Preset Changed To