22 RT-SVP07B-EN
General Status Display
Bias
0 deg F ___________ Setup
Zone Control Modulating Heat Gains
Proportional
10.0 % F ___________ Setup
Reset Time
DISABLE ___________ Setup
Rate Time
0 Sec ___________ Setup
Bias
0 deg F ___________ Setup
SZVAV Heating Control Gains
Proportional
8.0 % F ___________ Setup
Reset Time
1200 Sec ___________ Setup
Rate Time
0 Sec ___________ Setup
Bias
0 deg F ___________ Setup
Rapid DX Interstage Timing
30 Sec ___________ Setup
Default Setpoints
Supply Air Cooling
(VAV/SZVAV)
1
55 F / 50 F ___________ Setpoints
Supply Air Heating
(VAV/SZVAV)
1
100 F / 105 F ___________ Setpoints
SA Cool Deadband 8.0 F ___________ Setpoints
SA Heat Deadband 4.0 F ___________ Setpoints
DWU Initiate 67 F ___________ Setpoints
DWU Terminate 71 F ___________ Setpoints
Occupied Zone Cooling 74 F ___________ Setpoints
Occupied Zone Heating 71 F ___________ Setpoints
Zone Derived Setpoint 4 F ___________ Setpoints
Unoccupied Zone Cooling 85 F ___________ Setpoints
Unoccupied Zone Heating 60 F ___________ Setpoints
Unoccupied Zone MWU 72 F ___________ Setpoints
Rapid Restart Critical Temp
1
90 F ___________ Setpoints
Occ Dehumidification 60 % ___________ Setpoints
Occ Dehumid Hysteresis Offset 5 % ___________ Setpoints
Unocc Dehumidification 60 % ___________ Setpoints
Unocc Dehumid Hysteresis Offset 5 % ___________ Setpoints
Supply Air Reheat Setpoint 70 F ___________ Setpoints
Supply Air Reheat Deadband 4 F ___________ Setpoints
Maximum Reheat Valve Limit 85 % ___________ Setpoints
Dehumid Ovrd High Zone Temp 75 F ___________ Setpoints
Dehumid Ovrd Low Zone Temp 68 F ___________ Setpoints
Cond Coil Purge Interval 90 Min ___________ Setpoints
Occ Humidification 30 % ___________ Setpoints
Occ Humidification Hysteresis Offset 5 % ___________ Setpoints
Unocc Humidification 30 % ___________ Setpoints
Unocc Humidification Hysteresis Offset 5 % ___________ Setpoints
Economizer Cooling Setpoint Suppression (CV) 3 F ___________ Setpoints
Reference Enthalpy 25 BTU/LB ___________ Setpoints
Economizer Drybulb Enable Stpt 75 F ___________ Setpoints
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.