34 RT-SVP07B-EN
STATUS Menu
Condenser Sump Drain Relay: ON
Condenser Sump Drain Valve: CLOSED
Used With: DX Cooling w/Water-Cooled
Condensers
Possible Values:
Sump Drain Relay: ON, OFF
Sump Drain Valve: CLOSED, OPEN
“Relay” and “Valve” states are configurable based on the need to
hold water in the sump or drain it on power loss. See the IOM, and
“ Table 7: Sump Drain Valve States" on page 108 in Service Test
section for further information.
• Press Next/Previous keys to navigate.
Cond Sump Water Level Max Input: OPEN
Cond Sump Water Level Min Input: CLOSED
Used With: DX Cooling w/Water-Cooled
Condensers
Possible Values:
Max Input: CLOSED, OPEN
Min Input: CLOSED, OPEN
• Press Next/Previous keys to navigate.
External Sump Drain Request: INACTIVE
Used With: DX Cooling w/Water-Cooled
Condensers
Possible Values: ACTIVE, INACTIVE
• Press Next/Previous keys to navigate.
Reheat Coil Pumpout Relay: OFF
Reheat Coil Pumpout Valve: CLOSED
Used With: DX Cooling w/
Dehumidification
Possible Values:
Relay: ON, OFF
Valve: CLOSED, OPEN
• Press Next/Previous keys to navigate.
Dehumid Reheat Valve Position: 0%
Dehumid Cooling Valve Position: 100%
Used With: DX Cooling w/
Dehumidification
Possible Values:
Reheat Valve: 0 to Max Reheat Valve
Position Setpoint (see Setpoints
Menu)
Cooling Valve: 10 to 100%
• Press Next/Previous keys to navigate.
Active Outside Air Temperature 70.0°F
Low Ambient Comp Lockout Temp: 50°F
Used With: DX Cooling
Possible Values:
Active Outside Air Temp: -40 to
200.0ºF Lockout Temp: -20 to 80ºF
Default(s):
Standard: 50ºF
Low-Amb. w/Hot Gas Bypass: 0ºF
Low-Amb. w/o Hot Gas Bypass: 10ºF
• Press Next/Previous keys to navigate.