RT-SVP07B-EN 35
STATUS Menu
End of Submenu (NEXT) to Enter STATUS
Press Next/Previous keys to navigate.
ECONOMIZER STATUS SUBMENU SCREENS
Economizer Status Submenu
Press ENTER to View Data in This Submenu
Used With: Units w/Economizer
Press the Next key to skip this Submenu.
Air Economizing: ENABLED
Outside Air Damper Pos: Closing to 10%
Used With: Units w/Economizer
Possible Values:
Economizing: ENABLED/DISABLED
Damper Pos: 0 to 100%“Opening to” and ”Closing to” indicates direction.
Press Next/Previous keys to navigate.
Active Outside Air Enthalpy 29.5 BTU/LB
ECEM Return Air Enthalpy 34.0 BTU/LB
Used With: Units w/Economizer
Possible Values:
OA Enthalpy: 10 to 35 BTU/LB
RA Enthalpy: 10 to 35 BTU/LB"Return Air Enthalpy" is displayed if Comparative Enthalpy or
Energy Recovery is installed.
Press Next/Previous keys to navigate.
Active Outside Air Temperature 86.0°F
ECEM Return Air Temperature 78.0°F
Used With: Units w/Economizer
Possible Values:
OA Temp: -40 to 200°F
RA Temp: -40 to 200°F"Return Air Temperature” is displayed if Comparative Enthalpy or
Energy Recovery is installed.
Press Next/Previous keys to navigate.
Active Outside Air Humidity 30 %RH
ECEM Return Air Humidity 62 %RH
Used With: Units w/Economizer
Possible Values:
OA Humidity: 10 to 90%
RA Humidity: 10 to 90%“Return Air Humidity” is displayed if Comparative Enthalpy or
Energy Recovery is installed.
Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
Press Next/Previous keys to navigate.