RT-SVP07B-EN 43
STATUS Menu
Active Econ DB Enable Setpoint From
HI (KEYPAD) SETPOINT MENU is 75°F
Used With: Units w/Economizer
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 40 to 90ºF• Press Next/Previous keys to navigate.
Active OA Damper Min Position STP From
HI (KEYPAD) SETPOINT MENU is 25%
Used With: Units w/0-25% Motorized
Damper, or Economizer and OA CFM
Compensation Function DISABLED or OA
Damper Min Position Setpoint Source
Selection is Not “HI (KEYPAD)
SETPOINT”
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 0 to 100%
• Press Next/Previous keys to navigate.
Active Min OA Flow Setpoint From
HI (KEYPAD) SETPOINT MENU is 34.2 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/o DCV Option
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK SETPOINT
Range: 0 to Max Unit Airflow
[See “Table 7. Max Unit Airflows" on page
90” in the Setpoints Section Below]
• Press Next/Previous keys to navigate.
Active Design Min OA Flow Setpoint From HI
(KEYPAD) SETPOINT MENU is 34.2 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV Option
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK SETPOINT
Range: 0 to Max Unit Airflow
[See “Table 7. Max Unit Airflows" on page
90” in the Setpoints Section]
• Press Next/Previous keys to navigate.