44 RT-SVP07B-EN
STATUS Menu
Active Min OA Flow Target From
VCM Module is 120.5 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV Option
Possible Values:
VCM Module
BAS/NETWORK
Range: 0 to Max Unit Airflow
[See “Table 7. Max Unit Airflows" on page
90” in the Setpoints Section]
• Press Next/Previous keys to navigate.
Active Supply Air Pressure STP From
HI (KEYPAD) SETPOINT MENU is 2.0 IWC
Used With: VVDA Units
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK SETPOINT
Range: 0.7 to 5.1 IWC• Press Next/Previous keys to navigate.
Active Supply Air Pressure Setpoints
High Limit: 4.0 IWC Deadband: 0.5 IWC
Used With: VVDA or Units w/Supply Air
Pressure Sensor Present
Possible Values:
High Limit: 1.2 to 4.7 IWC
Deadband: 0.1 to 2.0 IWC
• Press Next/Previous keys to navigate.
Active Space Pressure Setpoint From
HI (KEYPAD) SETPOINT MENU is 0.08 IWC
Used With: Units w/Statitrac
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK SETPOINT
Range: -0.2 to 0.30 IWC• Press Next/Previous keys to navigate.
Active Space Pressure Deadband 0.1 IWC
Used With: Units w/Statitrac
Possible Values: 0.02 to 0.20 IWC
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.