RT-SVP07B-EN 49
STATUS Menu
IntelliPak II Config Input: CLOSED
Dehumidification Config Input: OPEN
Used With: All Units
Possible Values: OPEN/CLOSED
• Press Next/Previous keys to navigate.
RTM Supply Airflow Proving: FLOW
RTM Exhaust Airflow Proving: FLOW
Used With: All Units
Possible Values: Flow, No Flow
Bottom Left Field:
RTM Exhaust Airflow Proving
RTM Return Airflow Proving
“RTM Exhaust…” shown for Power Exhaust w/o Return Fan.
“RTM Return…” shown for Power Exhaust w/ Return Fan.
• Press Next/Previous keys to navigate.
RTM Remote Min Position Pot Input 0 %
Used With: Units w/Outside Air Damper
and Minimum Position Source is RTM.
Possible Values: 0 to 100%
Note: If potentiometer input is out of range (> 350 ohms) this
screen will not appear.
• Press Next/Previous keys to navigate.
RTM Supply Air Pressure Input 2.1 IWC
Used With: VVDA or Units w/Supply Air
Pressure is present.
Possible Values: 0 to 5.0 IWC
• Press Next/Previous keys to navigate.
RTM Outside Air Humidity 55 %
ECEM Return Air Humidity 46 %
Used With: Units w/Economizer Option
Possible Values: 10 to 90%
“OA Humidity” shown only if comparative enthalpy installed.
“RA Humidity” shown only if comparative enthalpy installed, or
non-IpakII units with humidification control.
• Press Next/Previous keys to navigate.
RTM Space Humidity 10 %
Used With: Units w/Dehumid. or Humid.
Option
Possible Values: 10 to 90%
• Press Next/Previous keys to navigate.
ECEM Space Pressure Input 0.08 IWC
Used With: Units w/Statitrac Option
Possible Values: -0.67 to 0.67 IWC
• Press Next/Previous keys to navigate.