Table 69. Supply fan VFD programming parameters (continued)
Menu ID
Description Parameter Setting
Application
Functions
22-60
Broken Belt
Function
[2] Trip for FC Fans (Digit 14=1, 2, 3, 4, 5, 6, 7, 8, 9, A)
[0] Disabled for DDP Fans (Digit 14=B through Z)
22-61
Broken Belt
Torque (%)
[10] 10%
22-62
Broken Belt
Delay (s)
[60] 60 Seconds
Table 70. Value for parameter 4–14 (Motor Speed High Limit)
DDP Fans - (Digit # 14 = B thru H, J thru N, P, R, T thru Z)
Digit # 5,6,7 (Unit Tonnage)
Digit # 2 = A, X Digit # 2 = F
(4 Pole) (6 Pole) (4 Pole) (6 Pole)
20,25
81
83
75
83
30 75 67
40 67 61
50-55 61 61
60 75 61
70-75 67 61
FC Fans - (Digit #14= 1 thru 9, A)
20 - 75 60
FC Fans - (Digit #14= C thru G)
90 - 130 60