150
RT-SVX072A-EN
Table 72. Condenser fan VFD parameters
Menu ID
Descriptions Parameter Setting
Opera-
tion
display
0-01
Language [0] English US
0-03
Regional Settings [1] North American
0-06
Grid Type
Set to applicable unit power supply
[122] 440-480V/60Hz for 460V/60Hz units
[132] 525-600V/60Hz for 575V/60Hz units
For IT Grid (no ground connections) or Corner grounded Delta power supply systems, the
applicable voltage/Hz and IT-Grid or Delta should be selected.
0-40
[Hand on] - Key on
LCP
[0] Disabled
Load
and
motor
1-20
Motor Power (KW/HP) Per Motor Nameplate KW- HP
1-22
Motor Voltage (V) Per Motor Nameplate Voltage
1-23
Motor Frequency (HZ) Per Motor Nameplate Frequency
1-24
Motor Current (A) Per Motor Nameplate FLA
1-25
Motor Nominal Speed
(RPM)
Per Motor Nameplate RPM
1-73
Flying Start [1] Enabled
1-90
Motor Thermal
Protection
[4] ETR Trip1
Brakes
2-00
DC Hold / Preheat
Current (%)
[0] 0%
2-01
DC Brake Current (%) [0] 0%
2-04
DC Brake Cut in Speed [10] 10 Hz
Refer-
ence /
Ramps
3-02
Minimum Reference
(HZ)
[6] 6Hz
3-03
Maximum Reference
(HZ)
[60] 60Hz
3-15 Reference 1 Source
[11] Local bus reference
3-16 Reference 2 Source
[0] No function
3-17 Reference 3 Source
[0] No function
3-41
Ramp 1 Ramp up Time
(S)
[10] 10s
3-42
Ramp 1 Ramp down
Time (S)
[10] 10s
Limits /
Warn-
ings
4-12
Motor Speed Low
Limit [HZ]
[6] 6Hz
4-14
Motor Speed High
Limit (Hz)
[60] 60Hz
4-18
Current Limit (%) [100] 100% for 1HP Motor
4-19
Max Output
Frequency (Hz)
[60] 60Hz
Digital
5-10
Terminal 18 Digital
Input
[0] No Operation
5-12
Terminal 27 Digital
Input
[0] No Operation
5-13
Terminal 29 Digital
Input
[0] No Operation