CLCH-SVX07C-EN 69
Component Installation Requirements
Table 19. Energy recovery recirculation parallel damper
Unit size A (in) B (in) Damper qty Torque (in-lb.)
Actuator torque
(max) (in-lb.) Actuator qty Linkage
3 16.00 13.97 1 10.9 42 1 No
4 28.50 13.97 1 19.4 42 1 No
6 28.50 13.97 1 19.4 42 1 No
8 35.00 13.97 1 23.8 42 1 No
10 46.00 13.97 1 31.2 42 1 No
12 51.00 13.97 1 34.6 42 1 No
14 56.50 13.97 1 38.4 160 1 No
17 56.50 13.97 1 38.4 160 1 No
21 64.50 13.97 1 43.8 160 1 No
25 64.50 13.97 1 43.8 160 1 No
30 78.00 13.97 1 53.0 160 1 No
35 84.50 13.97 1 57.4 160 1 No
40 97.00 13.97 1 65.9 160 1 No
50 110.00 13.97 1 74.7 160 1 No
Table 20. Energy recovery bypass opposed blade damper
Unit size A (in) B (in) Damper qty Torque in-lb.
Actuator Torque
(max) (in-lb.) Actuator qty Linkage
3 - 8 18.00 8.22 1 5.10 42 1 No
8 - 14 32.00 8.22 1 9.10 42 1 No
10 - 17 41.75 8.22 1 11.90 42 1 No
12 - 21 53.50 8.22 1 15.30 42 1 No
21 - 50 52.50 13.97 1 25.50 160 1 No
17, 21 61.50 8.22 1 17.60 42 1 No
21 - 30 66.00 8.22 1 18.80 42 1 No
25 - 50 65.00 13.97 1 31.50 160 1 No
21 70.00 8.22 1 20.00 42 1 No
35 - 50 84.50 13.97 1 41.00 160 1 No
35 - 50 75.00 13.97 1 36.40 160 1 No
40 - 50 102.00 13.97 1 49.50 160 1 No
50 113.00 13.97 1 54.80 160 1 No