104
2.. References and Limits
# Parameter Factory Setting Range Changes 4-Setup Conversion Data
Description during operation Index Type
200
Output Frequency Range
0 - 120 Hz 0 - 1000 Hz No Yes 0 5
201
Output Frequency Low Limit
Fans=6 Hz, Pumps=18 Hz 0.0 - par. 202 Yes Yes -1 6
202
Output Frequency High Limit
60 Hz par. 201 - par. 200 Yes Yes -1 6
203
Reference Handling
LINKED TO HAND/AUTO Yes Yes 0 5
204
Minimum Reference
Fans=6 Hz, Pumps=18 Hz 0.000-Ref
MAX
Yes Yes -3 4
205
Maximum Reference
000060.000 Hz Ref
MIN
-999.999,999 Yes Yes -3 4
206
Ramp-up Time
Fans=60 sec., Pumps=10 sec. 1 - 3600 sec. Yes Yes 0 7
207
Ramp-down Time
Fans=60 sec., Pumps=10 sec. 1 - 3600 sec. Yes Yes 0 7
208
Automatic Ramp-up/down
ENABLE Yes Yes 0 5
209
Jog Frequency
10.0 Hz par. 201 - par. 202 Yes Yes -1 6
210
Reference Type
EXTERNAL PRESET Yes Yes 0 5
211
Preset Reference 1
0.00% -100.00 - 100.00 % Yes Yes -2 3
212
Preset Reference 2
0.00 % -100.00 - 100.00 % Yes Yes -2 3
213
Preset Reference 3
0.00 % -100.00 - 100.00 % Yes Yes -2 3
214
Preset Reference 4
0.00 % -100,00 - 100,00 % Yes Yes -2 3
215
Current Limit
Depends on the unit 0 - I [A] Yes Yes -1 6
216
Frequency Bypass Bandwidth
DISABLED 0 - 120 Hz Yes Yes 0 6
217
Frequency Bypass 1
120.0 Hz 0.0 - par. 200 Yes Yes -1 6
218
Frequency Bypass 2
120.0 Hz 0.0 - par. 200 Yes Yes -1 6
219
Frequency Bypass 3
120.0 Hz 0.0 - par. 200 Yes Yes -1 6
220
Frequency Bypass 4
120.0 Hz 0.0 - par. 200 Yes Yes -1 6
221
Warning: Low Current
0.0 A 0.0 - par. 222 Yes Yes -1 6
222
Warning: High Current, I
I [A] Par. 221 - I [A] Yes Yes -1 6
223
Warning: Low Frequency
0.0 Hz 0.0 - par. 224 Yes Yes -1 6
224
Warning: High Frequency
120.0 Hz Par. 223 - par. 200/202 Yes Yes -1 6
225
Warning: Low Reference
-999,999.999 Hz -999,999.999 - par. 226 Yes Yes -3 4
226
Warning: High Reference
999,999.999 Hz Par. 225 - 999,999.999 Yes Yes -3 4
227
Warning: Low Feedback
-999,999.999 Hz -999,999.999 - par. 228 Yes Yes -3 4
228
Warning: High Feedback
999,999.999 Hz Par. 227 - 999,999.999 Yes Yes -3 4
1.. Load and Motor
# Parameter Factory Setting Range Changes 4-Setup Conversion Data
Description During Operation Index Type
100
Configuration
OPEN LOOP No Yes 0 5
101
To rque Characteristics
AEO FUNCTION No Yes 0 5
102
Motor Power
Depends on the unit 0.25 - 500 kW No Yes -2 6
103
Motor Voltage
Depends on the unit 200 - 575 V No Yes 0 6
104
Motor Frequency
60 Hz 24 - 1000 Hz No Yes 0 6
105
Motor Current
Depends on the unit 0.01 - I No Yes -2 7
106
Rated Motor Speed
Depends on 100 - 60000 rpm No Yes 0 6
par. 102 Motor power
107
Automatic Motor Adaptation, AMA
NO AMA No No 0 5
108
Start Voltage of Parallel Motors
Depends on par. 103 0.0 - par. 103 Yes Yes -1 6
109
Resonance Dampening
100% 0 - 500 % Yes Yes 0 6
110
High Br eakaway Torque
OFF 0.0 - 0.5 sec. Yes Yes -1 5
111
Start Delay
000.0 s 0.0 - 120.0 sec. Yes Yes -1 6
112
Motor Preheater
DISABLE Yes Yes 0 5
113
Motor Preheater DC Current
50% 0 - 100 % Yes Yes 0 6
114
DC Braking Current
50% 0 - 100 % Yes Yes 0 6
115
DC Braking Time
10.0 s 0.0 - 60.0 sec. Yes Yes -1 6
116
DC Brake Cut-in Frequency
OFF 0.0 - par. 202 Yes Yes -1 6
117
Motor Thermal Protection
ETR TRIP 1 Yes Yes 0 5
118
Motor Power Factor (Cos
Æ
)
0.75 0.50 - 0.99 No Yes -2 3