103
0.. Operation and Display
# Parameter Factory Setting Range Changes 4-Setup Conversion Data
Description During Operation Index Type
001
Language
ENGLISH Yes No 0 5
002
Active Setup
SETUP 1 Yes No 0 5
003
Copying of Setups
NO COPY No No 0 5
004
LCP Copy
NO COPY No No 0 5
005
Max Value of User -defined Readout
100.000 0 - 999.999,999 Yes Yes -2 4
006
Unit for User-defined Readout
%YesYes05
007
Big Display Readout
FREQUENCY, % Yes Yes 0 5
008
Small Display Readout 1.1
REFERENCE, % Yes Yes 0 5
009
Small Display Readout 1.2
MOTOR CURRENT, A Yes Yes 0 5
010
Small Display Readout 1.3
POWER, HP Yes Yes 0 5
011
Unit of Local Reference
% OF F MAX Yes Yes 0 5
012
Hand Start on LCP
ENABLE Yes Yes 0 5
013
OFF/STOP on LCP
ENABLE Yes Yes 0 5
014
Auto Start on LCP
ENABLE Yes Yes 0 5
015
Reset on LCP
ENABLE Yes Yes 0 5
016
Lock for Data Change
NOT LOCKED Yes Yes 0 5
017
Operating State at Power-up
AUTO RESTART Yes Yes 0 5
Factory Settings (continued)
Changes During Operation:
Yes means that the parameter can be changed while the drive is in
operation. No means that the drive must be stopped before a change
can be made.
4-Setup:
Yes means that the parameter can be programmed individually in
each of the four setups. The same parameter can have four different
data values. No means that the data value will be the same in all four
setups.
Conversion Index:
This number refers to a conversion figure to be used when writing or
reading to or from the drive by means of serial communication.
Since a parameter value can only be transferred as a whole number, a
conversion factor must be used to transfer decimals.
Example:
Parameter 201: Minimum Frequency, conversion factor 0.1. If
parameter 201 is to be set to 10 Hz, a value of 100 must be
transferred, since a conversion factor of 0.1 means that the transferred
value will be multiplied by 0.1. A value of 100 will, therefore, be
understood as 10.0.
Data type:
Data type shows the type and length of the packet.
Conversion Index Conversion Factor
74 3.6
2 100.0
1 10.0
0 1.0
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
Data type Description
3 Integer 16
4 Integer 32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9 Text string
Conversion Index Factors
Data Type Descriptions