106
4.. Application Functions
# Parameter Factory Setting Range Changes 4-Setup Conversion Data
Description During Operation Index Type
400
Reset Function
INFINITE AUTOMATIC Yes Yes 0 5
401
Automatic Restart Time
10 sec. 0 - 600 sec. Yes Yes 0 6
402
Flying Start
Fans=ENABLE, Pumps=DISABLE Yes Yes -1 5
403
Sleep Mode Timer
OFF 0 - 300 sec. Yes Yes 0 6
404
Sleep Frequency
0 Hz Min freq - Par. 405 Yes Yes -1 6
405
Wake up Frequency
60 Hz Par. 404 - max freq Yes Yes -1 6
406
Boost Setpoint
100% 0 - 200 % Yes Yes 0 6
407
Switching Frequency
Depends on the unit 3.0 - 14.0 kHz Yes Yes 2 5
408
Interference Reduction Method
ASFM Yes Yes 0 5
409
Function in Case of No Load
WARNING Yes Yes 0 5
410
Function at Phase Loss
TRIP Yes Yes 0 5
411
Function at Over Temp
TRIP Yes Yes 0 5
412
Trip Delay Overcurrent
OFF 0 - 60 sec. Yes Yes 0 5
413
Minimum Feedback
0.000 -999,999.999 - FB
MIN
Yes Yes -3 4
414
Maximum Feedback
100.000 FB
MIN
- 999,999.999 Yes Yes -3 4
415
Units Relating to Closed Loop
%YesYes-15
416
Feedback Conversion
LINEAR Yes Yes 0 5
417
Feedback Calculation
MAXIMUM Yes Yes 0 5
418
Setpoint 1
0.000 Min to max fdbk. Yes Yes -3 4
419
Setpoint 2
0.000 Min to max fdbk. Yes Yes -3 4
420
PID Normal/Inverse Control
NORMAL Yes Yes 0 5
421
PID Anti Windup
ENABLE Yes Yes 0 5
422
PID Start-up Frequency
0 Hz Min. to max. freq. Yes Yes -1 6
423
PID Proportional Gain
0.30 0.00 - 10.00 Yes Yes -2 6
424
PID Integral Time
OFF 0.01 - 9999.00 s. (Off) Yes Yes -2 7
425
PID Differentiation Time
OFF 0.0 (Off) - 10.00 sec. Yes Yes -2 6
426
PID Differentiation Gain Limit
5.0 5.0 - 50.0 Yes Yes -1 6
427
PID Lowpass Filter Time
0.01 0.01 - 10.00 Yes Yes -2 6