5.. Serial Communication
# Parameter Factory Setting Range Changes 4-Setup Conversion Data
Description during operation Index Type
500
Protocol
FC Yes Yes 0 5
501
Address
001 Depends on par. 500 Yes No 0 5
502
Baudrate
9600 BAUD Yes No 0 5
503
Coasting
LOGIC OR Yes Yes 0 5
504
DC-brake
LOGIC OR Yes Yes 0 5
505
Start
LOGIC OR Yes Yes 0 5
506
Reversing
DIGITAL INPUT Yes Yes 0 5
507
Selection of Setup
LOGIC OR Yes Yes 0 5
508
Selection of Preset Reference
LOGIC OR Yes Yes 0 5
509
Data Read-out: Reference %
No No -1 3
510
Data Read-out: Reference Unit
No No -3 4
511
Data Read-out: Feedback
No No -3 4
512
Data Read-out: Frequency
No No -1 6
513
User Defined Read-out
No No -2 7
514
Data Read-out: Current
No No -2 7
515
Data Read-out: Power, kW
No No 1 7
516
Data Read-out: Power, HP
No No -2 7
517
Data Read-out: Motor Voltage
No No -1 6
518
Data Read-out: DC Link Voltage
No No 0 6
519
Data Read-out: Motor temp.
No No 0 5
520
Data Read-out: TR1 Temp.
No No 0 5
521
Data Read-out: Digital Input
No No 0 5
522
Data Read-out: Terminal 53, Analog Input
No No -1 3
523
Data Read-out: Terminal 54, Analog Input
No No -1 3
524
Data Read-out: Terminal 60, Analog Input
No No -1 3
525
Data Read-out: Pulse Reference
No No -1 7
526
Data Read-out: External Reference %
No No -1 3
527
Data Read-out: Status Word, Hex
No No 0 6
528
Data Read-out: Heat Sink Temperature
No No 0 5
529
Data Read-out: Alarm Word, Hex
No No 0 7
530
Data Read-out: Control Word, Hex
No No 0 6
531
Data Read-out: Warning Word, Hex
No No 0 7
532
Data Read-out: Extended Status Word, Hex
No No 0 7
533
Display Text Line 1
No No 0 9
534
Display Text Line 2
No No 0 9
535
Bus Feedback 1
00000 No No 0 3
536
Bus Feedback 2
00000 No No 0 3
537
Data Read-out: Relay Status
No No 0 5
555
Bus Time Interval
60 sec. 1 to 99 sec. Yes Yes 0 5
556
Bus Time Interval Function
NO FUNCTION Yes Yes 0 5
560
N2 Overide Release Time
OFF 1 to 65534 sec. Yes Yes 0 5
565
FLN Bus Time Interval
60 sec. 1 to 65534 sec. Yes Yes 0 5
566
FLN Bus Time Interval Function
OFF Yes Yes 0 5
570
Modbus Parity & Message Framing
NO PARITY Yes Yes 0 5
571
Modbus Communication Timeout
100 ms 10 to 2000 msec. Yes Yes 1 6