EasyManua.ls Logo

Trane TR1 6016 - Power Connections and Wire Gauges

Trane TR1 6016
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Power Connections
1. Make all power connections with 75
o
C rated copper wiring.
2. Conduit entry must be from the bottom on all drives. Conduit entries
are provided on smaller drives. For drives with auxiliary
enclosures, refer to the dimensional drawings provided for conduit
entry locations.
3. To meet UL requirements, install the metalgrounding plate in all
drives that have a plastic bottom. Install the grounding plate just
above the plastic bottom. Ground the metal plate to the chassis and
ground the conduit to the metal plate.
4. The conduit entries provide strain relief for the wires in drives
mounted in NEMA 1 or NEMA 12 enclosures. With chassis
mounted drives, the power and control wires must have strain
relief supplied by the installer. D
O NOT rely on the terminal blocks to
provide strain relief.
All current ratings are in amps.
460 VAC Input Current/Wire Gage
550 - 600 VAC Input Current/Wire Gage
380 VAC Input Current/Wire Gage
Model
Drive Input
Current
Maximum
AWG
6002 2.3 10
6003 2.6 10
6004 3.8 10
6006 5.9 10
6008 8.8 10
6011 11.1 10
6016 16.6 6
6022 21.4 6
6027 26.3 6
6032 31.2 2
6042 39.9 2
6052 50.6 1/0
6062 60.4 1/0
6072 75 1/0
6100 92.4 3/0
6125 117 3/0
6150 134 4/0
6175 179 2 x 4/0
6225 226 2 x 4/0
6275 270 2 x 4/0
200 - 208 VAC Input Current/Wire Gage
Model
Drive Input
Current
Maximum
AWG
6002 6.3 10
6003 7.3 10
6004 10.4 10
6006 16.8 10
6008 23.8 6
6011 32.2 6
6016 48.3 6
6022 61.9 2
6027 78.2 2
6032 92.0 0
6042 117.0 1/0
6052 139.2 3/0
6062 165.5 4/0
Model
Drive Input
Current
Maximum
A
WG
6002 2.8 10
6003 3.8 10
6004 5.3 10
6006 9.1 10
6008 12.2 10
6011 15 10
6016 24 6
6022 32.0 6
6027 37.5 6
6032 44 6
6042 60 2
6052 72 2
6062 89 2
6072 104 1/0
6102 145 2/0
6122 174 3/0
6150 206 2x1/0
6152 206 2x1/0
6172 256 2x1/0
6175 256 2x1/0
6222 317 2x3/0
6225 317 2x3/0
6272 366 2x4/0
6275 366 2x4/0
6350 467 3x1/0
6352 467 3x1/0
6400 584 3x3/0
6500 648 3x3/0
6550 734 3x4/0
Model
Drive Input
Current
Maximum
A
WG
6002 2.5 10
6003 3.4 10
6004 4.8 10
6006 8.3 10
6008 10.6 10
6011 14 10
6016 21 6
6022 27.6 6
6027 34 6
6032 41 6
6042 53 2
6052 64 2
6062 77 2
6072 104 1/0
6102 128 2/0
6122 157 3/0
6150 185 2x1/0
6152 185 2x1/0
6172 236 2x1/0
6175 236 2x1/0
6222 304 2x3/0
6225 304 2x3/0
6272 356 2x4/0
6275 356 2x4/0
6350 431 3x1/0
6352 431 3x1/0
6400 526 3x3/0
6500 581 3x3/0
6550 668 3x4/0
WARNING
!
Induced Voltage!
Run output motor cables from multiple drives
separately. Induced voltage from output motor
cables run together can charge equipment
capacitors even with the equipment turned off
and locked out. Failure to run output motor
cables separately could result in death or
serious injury.
Current ratings are in Amps

Table of Contents