Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
200 to 208 VAC Auxiliary Control Panel Tightening Torques
200 to 240 VAC Terminal Tightening Torque
380 to 460 VAC Terminal Tightening Torque
Max. Drive
Output Current
Torque
in-lbs (Nm)
6.9 5 (0.6)
7.8 5 (0.6)
11 5 (0.6)
17.5 5 (0.6)
26 17 (1.8)
33 17 (1.8)
48.3 28 (3.0)
62.1 28 (3.0)
78.2 28 (3.0)
92 35 (4.0)
115 100 (11.3)
143 100 (11.3)
170 100 (11.3)
Max. Drive
Output Current
Torque
in-lbs (Nm)
Max. Drive
Output Current
Torque
in-lbs (Nm)
to 10 5 (0.6) 147 100 (11.3)
16 5 (0.6) 177 100 (11.3)
24 17 (1.8) 212 100 (11.3)
32 17 (1.8) 260 100 (11.3)
37.5 17 (1.8) 315 100 (11.3)
44 28 (3.0) 368 100 (11.3)
61 28 (3.0) 487 372 (42.0)
73 28 (3.0) 594 372 (42.0)
90 28 (3.0) 649 372 (42.0)
106 100 (11.3) 746 372 (42.0)
Terminal Tightening Torque
Tighten terminals connecting the drive input power, output to the
motor(s) and ground to the values shown in the tables below. Drives
with 200 to 240 volts of 88 amps and less, and drives with 380 to 600
volts of 90 amps and less, have removable terminal blocks with
screws. Larger drives have fixed bolts. (See the drive nameplate for
maximum drive output current.)
All current ratings are in amps.
200-208 V Hp
Rating
Overload
Relay
In/Out Power
Terminal
CTK Breaker
Main Disco
Switch
Drive Disco
Switch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Ground
Terminal
1
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
1 1/2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
3
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
5
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 45 (5.1) 45 (5.1)
7 1/2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 45 (5.1) 45 (5.1)
10
17 (1.9) 35 (4.0) 22 (2.5) 7 (.8) 7 (.8) 45 (5.1) 45 (5.1) 45 (5.1)
15
40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 45 (5.1) 45 (5.1) 50 (5.6)
20
40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 120 (13.6) 120 (13.6) 50 (5.6)
25
40 (4.5) 175 (19.8) 44 (5) 55 (6.2) 55 (6.2) 120 (13.6) 275 (30.1) 50 (5.6)
30
40 (4.5) 175 (19.8) 44 (5) 70 (7.9) 70 (7.9) 120 (13.6) 275 (30.1) 50 (5.6)
40
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
50
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
60
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) N/A 275 (30.1)
550 to 600 VAC Terminal Tightening Torque
Max. Drive
Output Current
Torque
in-lbs (Nm)
to 11 5 (0.6)
27 17 (1.8)
41 28 (3.0)
77 35 (4.0)
144 100 (11.3)
289 100 (11.3)
Terminal Tightening Torque for Optional
Auxiliary Control Panels
For drives with an optional auxiliary control panel enclosure, tighten
terminal connections in accordance with the tables provided.