EasyManua.ls Logo

Trane TR1 6016 - Page 15

Trane TR1 6016
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
230 to 240 VAC Auxiliary Control Panel Tightening Torques
230-240 V Hp
Rating
Overload
Relay
In/Out Power
Terminal
CTK Bre aker
Main Disco
Switch
Drive Disco
Switch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Ground
Terminal
1
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
1 1/2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
3
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
5
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
7 1/2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 45 (5.1) 45 (5.1)
10
17 (1.9) 35 (4.0) 22 (2.5) 7 (.8) 7 (.8) 45 (5.1) 45 (5.1) 45 (5.1)
15
40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 45 (5.1) 45 (5.1) 50 (5.6)
20
40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 120 (13.6) 120 (13.6) 50 (5.6)
25
40 (4.5) 175 (19.8) 44 (5) 55 (6.2) 18 (2) 120 (13.6) 275 (30.1) 50 (5.6)
30
40 (4.5) 175 (19.8) 275 (30.1) 70 (7.9) 55 (6.2) 275 (31.1) 275 (30.1) 50 (5.6)
40
40 (4.5) 175 (19.8) 275 (30.1) 375 (42.4) 70 (7.9) 275 (31.1) N/A 50 (5.6)
50
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
60
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) N/A 275 (30.1)
380-460 V Hp
Rating
Overload
Relay
In/Out Power
Terminal
CTK Breaker
Main Disco
Switch
Drive Disco
Switch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Ground
Terminal
1
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 25 (2.8) 45 (5.1)
1 1/2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 25 (2.8) 45 (5.1)
2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 25 (2.8) 45 (5.1)
3
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 25 (2.8) 45 (5.1)
5
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 25 (2.8) 45 (5.1)
7 1/2
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 25 (2.8) 45 (5.1)
10
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 25 (2.8) 45 (5.1)
15
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 45 (5.1) 45 (5.1)
20
17 (1.9) 35 (4.0) 22 (2.5) 7 (.8) 7 (.8) 45 (5.1) 45 (5.1) 45 (5.1)
25
17 (1.9) 35 (4.0) 22 (2.5) 18 (2) 7 (.8) 45 (5.1) 45 (5.1) 45 (5.1)
30
40 (4.5) 35 (4.0) 22 (2.5) 18 (2) 18 (2) 45 (5.1) 45 (5.1) 50 (5.6)
40
40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 45 (5.1) 120 (13.6) 50 (5.6)
50
40 (4.5) 175 (19.8) 44 (5) 55 (6.2) 18 (2) 120 (13.6) 120 (13.6) 50 (5.6)
60
40 (4.5) 175 (19.8) 44 (5) 70 (7.9) 55 (6.2) 120 (13.6) 275 (30.1) 50 (5.6)
75
40 (4.5) 175 (19.8) 275 (30.1) 375 (42.4) 70 (7.9) 275 (31.1) N/A 50 (5.6)
100
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
125
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 275 (30.1)
150
200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) 500 (56.5) 275 (30.1)
200
200 (22.6) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 450 (50.8) 500 (56.5) 275 (30.1)
250
375 (42.4) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 450 (50.8) 275 (30.1) 275 (30.1)
300
375 (42.4) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 375 (42.4) 375 (42.4) 275 (30.1)
380 to 460 VAC Auxiliary Control Panel Tightening Torques
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
Terminal Tightening Torque for Optional Auxiliary Control Panels (continued)

Table of Contents