4.4 Extended Status Words
Bit Hex Dec
Parameter 16
-94 Ext.
Status Word
Parameter 16-95
Ext. Status
Word 2
01 1 Ramping O
1 2 2 AMA running Hand/Auto
2 4 4 Start CW/CCW 0
38 8 0 0
410 16 0 0
520 32
Feedback
high
0
6 40 64 Feedback low 0
780 128
Output
current high
Control Ready
8100 256
Output
current low
Drive Ready
9200 512
Output
frequency
high
Quick Stop
10 400 1024
Output
frequency low
DC Brake
11 800 2048 0 Stop
12 1000 4096 0 0
13 2000 8192 Braking
Freeze Output
Request
14 4000 16384 0 Freeze Output
15 8000 32768 OVC active Jog Request
16 10000 65536 AC brake Jog
17 20000 131072 0 Start request
18 40000 262144 0 Start
19 80000 524288
Reference
high
0
20 100000 1048576 Reference low Start Delay
21 200000 2097152 0 Sleep
22 400000 4194304 0 Sleep boost
23 800000 8388608 0 Running
24 1000000 16777216 0 Bypass
25 2000000 33554432 0 Fire Mode
26 4000000 67108864 0 External Interlock
27 8000000 134217728 0
Firemodelimi-
texceed
28 10000000 268435456 0 FlyStart Active
29 20000000 536870912 0 0
30 40000000 1073741824 0 0
31 80000000 2147483648
Database
busy
0
Table 4.3 Extended Status Words
4.5 List of Warnings and Alarms
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical, or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures. Unless specied otherwise, disconnect all
electrical power including remote disconnect and
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power cannot be inadvertently
energised. When it is necessary to work with live
electrical components, have a qualied licensed
electrician or other individual who has been trained in
handling live electrical components perform these tasks.
Failure to follow all of the recommended safety warnings
provided, could result in death or serious injury.
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if parameter 6-01 Live
Zero Timeout Function is congured. The signal on 1 of the
analog inputs is less than 50% of the minimum value
programmed for that input. This condition can be caused
by broken wiring or a faulty device sending the signal.
WARNING/ALARM 3, No motor
No motor is connected to the output of the frequency
converter. Check the cable connection between the
frequency converter and the motor.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
for a fault in the input rectier on the frequency converter.
Options are programmed at parameter 14-12 Function at
Mains Imbalance.
CAUTION
Live Electrical Components!
Troubleshooting
Check the supply voltage and supply currents to
the frequency converter.
WARNING/ALARM 7, DC overvoltage
If the DC-link voltage exceeds the limit, the frequency
converter trips after a time.
Troubleshooting
•
Extend the ramp time.
•
Activate functions in parameter 2-10 Brake
Function.
•
Activate overvoltage control in
parameter 2-17 Over-voltage Control.
Troubleshooting Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 99
4