3.12 Main Menu - Data Readouts - Group 16
3.12.1 16-0* General Status
16-00 Control Word
Range: Function:
0
*
[0 - 65535 ] View the control word sent from the frequency
converter via the serial communication port in
hex code.
Bit Bit = 0 Bit = 1
00 Preset reference option lsb –
01
Preset reference option 2
nd
bit of
preset references
–
02 DC brake Ramp
03 Coasting Enable
04 Quick stop Ramp
05 Freeze output Ramp
06 Ramp stop Start
07 No function Reset
08 No function Jog
09 Ramp 1 Ramp 2
10 Data not valid Valid
11 Relay_A not active Relay_A activated
12 Relay_B not active Relay_B activated
13 Choice of set-up lsb –
14 No function No function
15 No function Reversing
Table 3.6 Control Word
16-01 Reference [Unit]
Range: Function:
0 ReferenceFeed-
backUnit
*
[-4999 - 4999
ReferenceFeed-
backUnit]
View the present reference
value applied on impulse
or analog basis in the unit
resulting from the congu-
ration
selected in
parameter 1-00
Congu-
ration Mode (Hz).
16-02 Reference [%]
Range: Function:
0 %
*
[-200 - 200 %] View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references.
16-03 Status Word
Range: Function:
0
*
[0 - 65535 ] View the status word sent from the frequency
converter via the serial communication port in
hex code.
Bit Bit = 0 Bit = 1
00 Control not ready Ready
01 Drive not ready Ready
02 Coasting Enable
03 No fault Trip
04 No warning Warning
05 Reserved –
06 No trip lock Trip lock
07 No warning Warning
08
Speed
≠
ref.
Speed = ref.
09 Local control Bus control
10 Out of range Frequency OK
11 Not running Running
12 No function No function
13 Voltage OK Above limit
14 Current OK Above limit
15 Thermal-level OK Above limit
Table 3.7 Status Word
16-05 Main Actual Value [%]
Range: Function:
0 %
*
[-200 - 200 %] View the 2 byte word sent with the status
word to the bus master reporting the
main actual value.
16-09 Custom Readout
Range: Function:
0 CustomRea-
doutUnit
*
[0 - 9999
CustomRea-
doutUnit]
View the user-dened readouts
as dened in
parameter 0-30 Custom Readout
Unit, parameter 0-31 Custom
Readout Min Value, and
parameter 0-32 Custom Readout
Max Value.
3.12.2 16-1* Motor Status
16-10 Power [kW]
Range: Function:
0 kW
*
[0 - 1000
kW]
Displays the actual motor power in kW.
The value shown is calculated on the basis
of the actual motor voltage and motor
current.
16-11 Power [hp]
Range: Function:
0 hp
*
[0 - 1000
hp]
View the actual motor power in hp. The
value shown is calculated based on the
actual motor voltage and motor current.
Parameters Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 79
3