5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to
dene
the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm; When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[61] Comparator 1 See parameter group 13-1* Comparators.
If comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[62] Comparator 2 See parameter group 13-1* Comparators.
If comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[63] Comparator 3 See parameter group 13-1* Comparators.
If comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[64] Comparator 4 See parameter group 13-1* Comparators.
If comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[65] Comparator 5 See parameter group 13-1* Comparators.
If comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[70] Logic rule 0 See parameter group 13-4* Logic Rules. If
logic rule 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[71] Logic rule 1 See parameter group 13-4* Logic Rules. If
logic rule 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[72] Logic rule 2 See parameter group 13-4* Logic Rules. If
logic rule 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[73] Logic rule 3 See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[74] Logic rule 4 See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[75] Logic rule 5 See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[80] SL digital
output A
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [38] Set dig. out. A high is
executed. The input goes low whenever
the smart logic [32] Action Set dig. out. A
low is executed.
[81] SL digital
output B
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [39] Set dig. out. B high is
executed. The input goes low whenever
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to
dene
the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm; When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
the smart logic [33] Action Set dig. out. B
low is executed.
[82] SL digital
output C
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [40] Set dig. out. C high is
executed. The input goes low whenever
the smart logic [34] Action Set dig. out. C
low is executed.
[83] SL digital
output D
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic [41] Action Set dig. out. D high is
executed. The input goes low whenever
the smart logic [35] Action Set dig. out. D
low is executed.
[160] No alarm The output is high when no alarm is
present.
[161] Running
reverse
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
running and reverse).
[165] Local ref.
active
The output is high when local reference
is activated by the [Hand on] key on the
LCP or by hand-on command of digital
input.
[166] Remote ref.
active
The output is high when remote
reference is activated by the [Auto on]
key on the LCP or by auto-on command
of digital input.
[167] Start
command
activ
The output is high when there is an
active start command (that is, via digital
input bus connection or [Hand on] or
[Auto on], and no stop command is
active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in hand on mode (as
indicated by the LED light above [Hand
on].
[169] Drive in auto
mode
The output is high when the frequency
converter is in auto on mode (as
indicated by the LED light above [Auto
on].
[190] No-Flow A no-ow condition has been detected.
See parameter group 22-2* No-Flow
Detection.
Parameters TR150 and TR170
52 02/2017 All rights reserved. BAS-SVP16B-EN