8-83 Slave Error Count
Range: Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
error telegrams, which the frequency
converter could not execute.
8-84 Slave Messages Sent
Range: Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
messages sent from the slave.
8-85 Slave Timeout Errors
Range: Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
slave timeout errors.
8-88 Reset FC port Diagnostics
Option: Function:
[0]
*
Do not reset
[1] Reset counter
3.8.7 8-9* Bus Feedback
8-94 Bus Feedback 1
Range: Function:
0
*
[-32768 -
32767 ]
Write feedback to this parameter via the serial
communication port. Select this parameter in
parameter 20-00 Feedback 1 Source or
parameter 20-03 Feedback 2 Source as a feedback
source. Hex value 4000 h corresponds to 100%
feedback/range is
±
200%.
8-95 Bus Feedback 2
Range: Function:
0
*
[-32768 -
32767 ]
Write a feedback to this parameter via the serial
communication port. This parameter must be
selected in parameter 20-00 Feedback 1 Source or
parameter 20-03 Feedback 2 Source as a feedback
source. The hexadecimal value 4000 h
corresponds to ±200% in 100% feedback/range.
Parameters TR150 and TR170
64 02/2017 All rights reserved. BAS-SVP16B-EN