16-54 Feedback 1 [Unit]
Range: Function:
0
ProcessCtrlUnit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View the feedback 1 value
resulting from the selection
of scaling in
parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
16-55 Feedback 2 [Unit]
Range: Function:
0
ProcessCtrlUnit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View the feedback 2 value
resulting from the selection
of scaling in
parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
3.12.5 16-6* Inputs and Outputs
16-60 Digital Input
Range: Function:
0
*
[0 -
65535 ]
View actual state of the digital inputs 18, 19, 27,
and 29.
Bit 0 Unused
Bit 1 Unused
Bit 2 Digital input terminal 29
Bit 3 Digital input terminal 27
Bit 4 Digital input terminal 19
Bit 5 Digital input terminal 18
Bit 6–15 Unused
Table 3.8 Bits Denition
16-61 Terminal 53 Setting
Option: Function:
View the setting of input terminal 53.
Current = 0
Voltage = 1
[0]
*
Current mode
[1] Voltage mode
16-62 Analog Input AI53
Range: Function:
1
*
[0 - 20 ] View the actual value at input 53.
16-63 Terminal 54 Setting
View the setting of input terminal 54.
Current = 0
Voltage = 1
Option: Function:
[0]
*
Current mode
[1] Voltage mode
16-64 Analog Input AI54
Range: Function:
1
*
[0 - 20 ] View the actual value at input 54.
16-65 Analog Output AO42 [mA]
Range: Function:
0 mA
*
[0 - 20 mA] View the actual value at output 42 in mA.
The value shown reects the selection in
parameter 6–90 Terminal 42 Mode and
parameter 6–91 Terminal 42 Analog Output.
16-66 Digital Output
Range: Function:
0
*
[0 -
15 ]
View the binary value of all digital outputs.
Denition:
X: Not used
0: Low
1: High
XX None used
X0 Terminal 42 not used, terminal 45
low.
X1 Terminal 42 not used, terminal 45
high.
0X Terminal 42 low, terminal 45 not
used.
0 Terminal 42 low, terminal 45 low.
1 Terminal 42 low, terminal 45 high.
1X Terminal 42 high, terminal 45 not
used.
10 Terminal 42 high, terminal 45 low.
11 Terminal 42 high, terminal 45 high.
Table 3.9 Binary Value of Digital Outputs
16-67 Pulse Input #29 [Hz]
Range: Function:
0
*
[0 - 130000 ] View the actual frequency rate on terminal 29.
16-71 Relay Output [bin]
Range: Function:
0
*
[0 - 65535 ] View the setting of the relay.
Parameters Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 81