Analog Input Scaling
Function Default Range AI53 AI54
Low voltage
scaling
0.07 V 0.00 – 10.00 V 6-10 6-20
High voltage
scaling
10.00 V 0.00 – 10.00 V 6-11 6-21
Low current
scaling
4.0 mA 0.00 – 20.00 mA 6-12 6-22
High current
scaling
20.00 mA 0.00 – 20.00 mA 6-13 6-23
Low reference
or FB scaling
0.000 -999,999.999 to 999,999.999 6-14 6-24
High reference
or FB scaling
100.000 -999,999.999 to 999,999.999 6-15 6-25
Filter time 0.001 s 0.001-10.000 s 6-16 6-26
Live zero Enabled Disabled or Enabled 6-17 6-27