13
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU007D-GB
Alarms
Message
Reset
Type
Unit Status Description
73
Alarms pCOe 5 IO
mismatch
Auto Unit On pCOextension5 is in default on Analog input #4
74 Alarm Drive Fault Manual Unit Off Variable Primary Flow Drive fault
75
Alarm Low Differential
Pressure ckt1
Auto Circuit 1 Off
Low Differential Pressure on circuit 1 (High
Pressure - Low Pressure)
76
Alarm Low Differential
Pressure ckt2
Auto Circuit 2 Off
Low Differential Pressure on circuit 2 (High
Pressure - Low Pressure)
77
Warning Cutout Supp
Heating
Auto Unit On
Information that Supplemental Heating is in cut
out
78 Warning LRTC limit ckt1 Auto Circuit 1 Limit Low Refrigerant Temperature cut-out on circuit 1
79 Warning LRTC limit ckt2 Auto Circuit 2 Limit Low Refrigerant Temperature cut-out on circuit 2
80
EVD EVO EXV synchro
Please wait
Auto Unit Off Expansion Valve is currently initiating

Other manuals for Trane Tracer CH535

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer CH535 and is the answer not in the manual?

Trane Tracer CH535 Specifications

General IconGeneral
BrandTrane
ModelTracer CH535
CategoryController
LanguageEnglish