EasyManua.ls Logo

Trane Tracer Concierge - Troubleshooting Air-Fi: WCI Does Not Join Network

Trane Tracer Concierge
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVN208G-EN 23
Troubleshooting and Common Questions
Troubleshooting Air-Fi
®
: WCI does not join network
See the Tracer Concierge for Small Buildings User Guide (BAS-SVU031) for additional
troubleshooting.
Possible cause Explanation/Resolution
Not enough time allowed
for joining
Give the WCI more time to join. If the network closes before the WCI has
joined, re-open if necessary by pressing the OPEN NET button on
another member WCI.
Wrong address For factory addressed WCIs, verify address is correct.
Verify each WCI address after installation.
If sensor is installed, check for error code at sensor.
Initiate network formation and resolve by exception.
No power Ensure that:
The WCI is wired correctly.
The corresponding controller is wired to equipment correctly and is
powered On.
Too much traffic Try a different channel by selecting a different net address or by using
Tracer TU. A better channel may be found by trial and error or by using
a purchased tool such as WiSpy.
Outside of radio range or
too many obstacles
Relocate WCI or add a repeater
Defective WCI Replace

Other manuals for Trane Tracer Concierge