BAS-SVN208G-EN 5
Installation Order
Installation Order
Hardware setup (Steps 1-8). See Tracer Concierge System Part 1 of 2: Hardware Setup
(BAS-SVN135*-EN).
Setup System Controller and display (Steps 9-17, this document).
Step 9: Verify Package Contents
Note: Tracer Concierge 2.0 requires System Controller 4.0 as of December 2016.
Step 10: Installation Checklist
Verify that hardware installation is complete:
Verify the System Controller panel is attached to the wall and power is wired to it.
Verify XM Module I/O terminations are wired appropriately per the submittal.
Verify System Controller Air-Fi
®
Wireless is addressed properly and/or the Air-Fi
Wireless Network Best Practice guide BAS-SVX55. See also Step 11.
Verify that any rooftop units and VAV boxes with Air-Fi Wireless are addressed
properly per the submittal and/or the Air-Fi Wireless Network Best Practice Guide
BAS-SVX55.
Verify the Ethernet Cable for the customer’s network is connected to System Controller
Ethernet Port 1 (if applicable).
Follow this best practice for ReliaTel BCI for Constant Volume Rooftops: install a duct
temperature probe (part number 4190-7020) in the return air duct and wire the sensor
to the BCI-R's space temperature input. Unless the HVAC system is a Changeover
System, in which case place the duct temperature probe in the return air duct, before/
upstream of the bypass damper.
Table 1. Packaged contents
Item Quantity
10.1 in. Display 1
Display power cord 1
Installation Instructions 1
User Guide 1
USB-to-Ethernet Adapter 1
VESA Mounting Bracket 1
Ethernet Cable 1

Other manuals for Trane Tracer Concierge