EasyManuals Logo

Trane TVR Pro CO 4TVY0229H8000AA User Manual

Trane TVR Pro CO 4TVY0229H8000AA
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #107 background imageLoading...
Page #107 background image
106
2.22 P5: Outdoor heat exchanger temperature protection
Digital display output
Description
Outdoor heat exchanger temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Outdoor heat exchanger temperature (T3) 65
o
C.
Recover condition: Outdoor heat exchanger temperature (T3) < 55
o
C.
Reset method: Resume automatically.
Possible causes
Outdoor unit stop valves are closed.
Temperature sensor not connected properly or has malfunctioned.
Indoor load too large.
System contains air or nitrogen.
Poor condenser heat exchange.
High pressure side blockage.
Main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TVR Pro CO 4TVY0229H8000AA and is the answer not in the manual?

Trane TVR Pro CO 4TVY0229H8000AA Specifications

General IconGeneral
Model Number4TVY0229H8000AA
CategoryAir Conditioner
BrandTrane
SeriesTVR Pro CO
Cooling Capacity22, 900 BTU/h
Refrigerant TypeR-410A
Voltage208/230V
Phase1
Sound Level (Outdoor Unit)72 dB
Operating Temperature Range (Cooling)14°F to 115°F
SEER Rating16 SEER
Warranty10 years

Related product manuals