2.10 F3, F5: Temperature sensor (T6B/T6A) error
Digital display output
Description
F3 indicates plate heat exchanger cooling refrigerant outlet temperature sensor (T6B) error.
F5 indicates plate heat exchanger cooling refrigerant inlet temperature sensor (T6A) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Temperature sensor T6A(B) is open or short-circuit.
Recover condition: Temperature sensor T6A(B) connection ports can detect load.
Reset method: Resume automatically.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TVR Pro CO 4TVY0229H8000AA and is the answer not in the manual?

Trane TVR Pro CO 4TVY0229H8000AA Specifications

General IconGeneral
Model Number4TVY0229H8000AA
CategoryAir Conditioner
BrandTrane
SeriesTVR Pro CO
Cooling Capacity22, 900 BTU/h
Refrigerant TypeR-410A
Voltage208/230V
Phase1
Sound Level (Outdoor Unit)72 dB
Operating Temperature Range (Cooling)14°F to 115°F
SEER Rating16 SEER
Warranty10 years