75
2.11 F6: Electronic expansion valve connection error
Digital display output
In the error code, 'x' is a placeholder for the EXV system, with 1 representing EXVA, 2 representing EXVB, and 3
representing EXVC.
Description
Electronic expansion valve connection error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: The main control board cannot receive the feedback signal of EXV.
Recover condition: The main control board can receive the feedback signal of EXV.
Reset method: When the main control board can receive the feedback signal of EXV, F6 flashes, a manual system
restart is required before the system can resume operation.
Possible causes
Electronic expansion valve coil not connected properly or has malfunctioned.
Damaged main PCB.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TVR Pro CO 4TVY0229H8000AA and is the answer not in the manual?

Trane TVR Pro CO 4TVY0229H8000AA Specifications

General IconGeneral
Model Number4TVY0229H8000AA
CategoryAir Conditioner
BrandTrane
SeriesTVR Pro CO
Cooling Capacity22, 900 BTU/h
Refrigerant TypeR-410A
Voltage208/230V
Phase1
Sound Level (Outdoor Unit)72 dB
Operating Temperature Range (Cooling)14°F to 115°F
SEER Rating16 SEER