This document is an installation, operation, and maintenance manual for Trane Odyssey™ split system air conditioners with Symbio™ controls. It covers heat pump condensers (R-410A) ranging from 5 to 20 tons, and R-22 dry charge units from 7.5 to 20 tons (60 Hz and 50 Hz).
The manual describes the proper procedures for installing, operating, and maintaining air-cooled split systems. These condensers are available with single or dual compressor options. Single compressor units feature a single refrigeration circuit, while dual compressor/dual circuit models offer true stand-by protection, automatically starting the second compressor if one fails. During light load conditions, only one compressor operates to save energy.
The manual provides detailed model number descriptions for heat pump condensers, breaking down each digit to specify unit function, tonnage, refrigerant type (R-22 or R-410A), voltage, refrigeration circuit/stage, design sequence, service digits, efficiency generation, controls (Symbio™), coil protection, and communication options.
Tonnage (60 Hz):
Tonnage (50 Hz):
Refrigerant:
Voltage:
Refrigeration Circuit/Stage:
Controls:
Coil Protection:
Communications Options:
The document also includes dimensional data with height, width, and depth measurements for various models, as well as detailed drawings showing service panel locations, refrigerant gauge access, and mounting holes. Unit weights are provided for both R-410A and R-22 units, including shipping and net maximum weights, and corner weights for proper lifting.
Refrigerant charging data and pressure curves are listed, including estimated charge levels at ARI rated line lengths (25 feet) for various matched sets of condensers and air handlers. It specifies liquid and vapor line diameters for each configuration.
The manual emphasizes proper pre-installation procedures, including unit inspection for shipping damage, testing for leaks (units are shipped with a nitrogen holding charge), and lifting recommendations with spreader bars to prevent damage. Clearances are critical for proper operation, with minimum distances specified for walls, shrubbery, privacy fences, and adjacent units. Snow belt recommendations advise raising the unit to prevent snow blockage.
Installation involves meticulous refrigerant piping procedures, adhering to R-410A pressure requirements (higher than R-22) and using only R-410A rated service equipment. Brazing must be done with a dry nitrogen purge to prevent contamination. System evacuation to 500 microns is required after leak checks.
Electrical wiring instructions cover unit power supply, low voltage wiring for thermostats or zone sensors, and Symbio™ controls connections. All wiring must comply with national and local electrical codes, and shielded twisted pairs are recommended for communication signals.
The Symbio™ 700 controls support a "Service Test Mode" to energize various system components for startup tasks or troubleshooting. This mode can be initiated through the controller user interfaces or the Symbio Service and Installation mobile application.
The manual outlines a comprehensive maintenance schedule:
Monthly Maintenance:
Annually (Cooling Season) Maintenance:
Coil Cleaning (Tube and Fin):
Control Circuit Features (Pre-Start Checks):
The manual includes a "Maintenance Log" to record monthly and annual inspection data, such as ambient temperature, evaporator entering air (dry and wet bulb), compressor suction and discharge pressures, superheat, and subcooling.
Warranty Information: The warranty covers commercial unitary equipment rated 25 tons and under, and related accessories. It includes a basic warranty of twelve (12) months from initial start-up or eighteen (18) months from shipment date for defects in material and manufacture. A replacement part is furnished without charge for manufacturing defects. The sealed motor-compressor is covered for a second through fifth year if it fails due to a manufacturing defect. Exclusions include local transportation, service labor, diagnosis calls, and damage due to accident, abuse, improper use, external causes, freezing, corrosion, erosion, or deterioration. The warranty is conditional on written notice of defect within thirty (30) days of discovery.