13
Service Facts
X343070P08
GROUND
TO PIN #4
TO PIN #5
A.C. VOLTS
#3
#4
#5
Q
uick
C
heck
M
otor
W
ill
N
ot
R
un
3. U
nplug
16
wire
low
voltage
harness
fr om
the
motor
.
J
umper
24 V
olts
A.C.
to
motor
low
voltage
plug
pins
#12
and
#15
and
pins
#1
and
#3
which
are
common
.
D
oes
motor
run
?
NO:
Go to step #4.
YES:
Fault is in the
16 wire low voltage
harness. Repair or
replace it.
4. I
s
the
line
voltage
to
the
motor
high
voltage
power
plug
pin
#4
and
pin
#5
correct
?
NO:
Correct line voltage fault.
YES:
Live voltage correct and
motor will not run.
Replace motor.
TO PIN #1 & #3